EVCO c-pro nano RACK User Manual
Page 35

C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL
Page 35
step of circuit 2 compressors (Neutral zone)
PG01 > 1
and
PC34 = 1
PC43
Maximum time of release for the further
step of circuit 2 compressors (Neutral zone)
60
0
999
Sec
IS-R2
Visible if
PG01 > 1
and
PC34 = 1
PC44
Differential for the inverter adjustment of
circuit 2 compressors
0.5
0.0
20.0
Bar
IS-R2
Visible if
PG01 > 1
and
PG16 = 1
PC45
Offset in relation to the suction setpoint for
inverter adjustment of circuit 2 compressors
0.0
-20.0
20.0
Bar
IS-R2
Visible if
PG01 > 1
and
PG16 = 1
PC46
Minimum value of the inverter of circuit 2
compressors
0.0
0.0
100.0
%
IS-R2
Visible if
PG01 > 1
and
PG16 = 1
PC47
SpeedUp time for the inverter of circuit 2
compressors
0
0
999
Sec
IS-R2
Visible if
PG01 > 1
and
PG16 = 1
PC48
Time within which the inverter changes
from minimum value to its maximum value
for the neutral zone adjustments of circuit 2
compressors
10
0
999
Sec
IS-R2
Visible if
PG01 > 1
and
PG16 = 1
PF32
Minimum value of discharging setpoint of
circuit 2 fans
1.0
PH03
SPF2
Bar
IS-R2
Visible if
PG01 > 1
and
PG30 = 0
PF33
Maximum value of discharging setpoint of
circuit 2 fans
25.0
SPF2
PH04
Bar
IS-R2
Visible if
PG01 > 1
and
PG30 = 0
PF34
Set the adjustment type for management of
circuit 2 fans
Sideband
(0)
Sideban
d (0)
Neutral
zone (1)
-
IS-R2
Visible if
PG01 > 1
and
PG30 = 0
PF36
IT integral time of the sideband adjustment
of circuit 2 fans
600
0
999
Sec
IS-R2
Visible if
PG01 > 1
and
PG30 = 0
and
PF34 = 0
PF37
PB proportional band for the sideband
adjustment of circuit 2 fans
0.5
0
20.0
Bar
IS-R2
Visible if
PG01 > 1
and
PG30 = 0
and
PF34 = 0
PF38
Value of the Zone for neutral zone
adjustment of circuit 2 fans
1.0
0
20.0
Bar
IS-R2
Visible if
PG01 > 1
and
PG30 = 0
and
PF34 = 1
PF40
Insertion / release time for the next fan in
neutral zone adjustment of circuit 2
10
0
999
Sec
IS-R2
Visible if
PG01 > 1
and
PG30 = 0
and
PF34 = 1