EVCO c-pro nano RACK User Manual
Page 44

C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL
Page 44
visibile if
PG01 > 1
Hd24
Set the position of the digital input
associated with the high pressure alarm on
the discharge pressure regulator of circuit 2
0
0
5(10)
n
CO-Hw
(10 if
expansion
is
enabled);
visibile if
PG01 > 1
Hd25
Set the position of the digital input
associated with the oil differential alarm for
compressors alarm of the circuit 2
0
0
5(10)
n
CO-Hw
(10 if
expansion
is
enabled);
visibile if
PG01 > 1
Hd26
Set the position of the digital input
associated with the common thermal alarm
for the fans of circuit 2
0
0
5(10)
n
CO-Hw
(10 if
expansion
is
enabled);
visibile if
PG01 > 1
Hd41
Set the position of the digital input
associated with the thermal alarm for
compressor 1
1
0
5(10)
n
CO-Hw
(10 if
expansion
is
enabled);
visibility
*1
Hd42
Set the position of the digital input
associated with the thermal alarm for
compressor 2
2
0
5(10)
n
CO-Hw
(10 if
expansion
is
enabled);
visibility
*1
Hd43
Set the position of the digital input
associated with the thermal alarm for
compressor 3
0
0
5(10)
n
CO-Hw
(10 if
expansion
is
enabled);
visibility
*1
Hd44
Set the position of the digital input
associated with the thermal alarm for
compressor 4
0
0
5(10)
n
CO-Hw
(10 if
expansion
is
enabled);
visibility
*1
Hd81
Set the position of the digital inputs
associated with the thermal alarm for fan 1
3
0
5(10)
n
CO-Hw
(10 if
expansion
is
enabled);
visibility
*2
Hd82
Set the position of the digital inputs
associated with the thermal alarm for fan 2
4
0
5(10)
n
CO-Hw
(10 if
expansion
is
enabled);
visibility
*2
Hd83
Set the position of the digital inputs
associated with the thermal alarm for fan 3
0
0
5(10)
n
CO-Hw
(10 if
expansion
is
enabled);
visibility
*2
Hd84
0
0
5(10)
n
CO-Hw
(10 if