EVCO c-pro nano RACK User Manual
Page 36

C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL
Page 36
PF44
Differential for the inverter adjustment of
circuit 2 fans
0.5
0.0
20.0
Bar
IS-R2
Visible if
PG01 > 1
and
PG46 = 1
PF45
Offset in relation to the suction setpoint for
inverter adjustment of circuit 2 fans
0.0
-20.0
20.0
Bar
IS-R2
Visible if
PG01 > 1
and
PG46 = 1
PF46
Minimum value of the inverter of circuit 2
fans
0.0
0.0
100.0
%
IS-R2
Visible if
PG01 > 1
and
PG46 = 1
PF47
SpeedUp time for the inverter of circuit 2
fans
2
0
999
Sec
IS-R2
Visible if
PG01 > 1
and
PG46 = 1
PF48
Time within which the inverter changes
from minimum value to its maximum value
for the neutral zone adjustments of circuit 2
fans
10
0
999
Sec
IS-R2
Visible if
PG01 > 1
and
PG46 = 1
PC01
Type of rotation used for compressors
management:
0: FIFO
1: LIFO
2: FIFO + hours of operation
3: LIFO + hours of operation
0 = FIFO
0
3
n
IS-C
PC02
Set the trigger way of the throttlings:
0: CppCpp / ppCppC
1: CCpppp / ppppCC
2: CppCpp / ppppCC
3: CCpppp / ppCppC
0 =
Cpp_Cpp
0
3
-
IS-C
PC03
Set the logic of relays used for the
throttlings of the compressors:
0: NC (norm. close). P. es Copeland
1: NO (norm.open). P. es. Feeders
1=NO
0
1
-
IS-C
PC04
Minimum time during which the
compressor must remain switched on even
if the switching off is required
10
0
999
Sec
IS-C
PC05
Minimum time during which the
compressor must remain switched off even
if the switching on is required
120
0
999
Sec
IS-C
PC06
Minimum time that must elapse between
two switching on of the same compressor
360
0
999
Sec
IS-C
PC07
Minimum time that must elapse between the
switching on of two different compressors
20
0
999
Sec
IS-C
PC08
Minimum time that must elapse between the
switching off of two different compressors
20
0
999
Sec
IS-C
PC09
Minimum time between the switching on of
the throttlings
20
0
999
Sec
IS-C
PC10
Minimum time between the switching off of
the throttlings
20
0
999
Sec
IS-C
PC11
Number of compressors that will be forced
if there is an alarm over the suction probe
of circuit 1
1
0
PG11
n
IS-C
PC31
Number of compressors that will be forced
if there is an alarm over the suction probe
of circuit 2
1
0
PG15
n
IS-C
Visible if
PG01 > 1
PC69
Timeout of compressors’starting from reset
mode
0
0
999
sec
IS-C
PC70
Enable compressors’ throttlings at high
pressures
0: NO
1: YES
0 (NO)
0
1
-
IS-C