C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL
Page 39
5: R410A
6: R507
PH32
Set the unit of measurement of temperature:
0: °Celsius
1: °Fahrenheit
0 (°C)
0
1
-
IS-V
PH33
Set the unit of measurement of pressure:
0: Bar
1: psi
0 (Bar)
0
1
-
IS-V
PH35
Enable load losses compensation on suction
line (neutral zone)
0: NO
1: YES
0 (NO)
0
1
-
IS-V
PH36
Load losses compensation factor
0.2
0.1
5.0
Bar
IS-V
PH40
Set the display in pressure or temperature
0: Pressure
1: Temperature
0
0
1
-
IS-V
PH43
Set the type of A/3 universal analogue input
2: NTC
3: 0-20mA
4: 4-20mA
5: reserved
4
4-20mA
2
5
-
IS-V
PH44
Set the type of A/4 universal analogue
2: NTC
3: 0-20mA
4: 4-20mA
5: reserved
4
4-20mA
2
5
-
IS-V
PH50
Set the display with the icons only
0: NO
1: YES
1 (SI)
0
1
-
IS-V
PH51
Set the display of numeric icons
0: NO
1: YES
1 (SI)
0
1
-
IS-V
PH52
Set the display of Evco icon
0: NO
1: YES
1 (SI)
0
1
-
IS-V
PA01
Enable the alarm of compressors’ operation
hours
No
No (0)
Si (1)
-
IS-S
PA02
Enable the alarm of fans’ operation hours
No
No (0)
Si (1)
-
IS-S
PA03
Set the activation delay of high pressure
suction alarms
1
0
999
Sec
IS-S
PA04
Set the detection delay of expansion alarm
5
0
999
Sec
IS-S
PA05
Set the activation delay of liquid level alarm
90
0
999
Sec
IS-S
PA06
Set the detection delay of the alarms over
suction and discharging probes
5
0
240
Sec
IS-S
PA07
Set the activation delay of low pressure
discharging alarm
30
0
999
Sec
IS-S
PA08
Set the activation delay of low pressure
suction alarms
30
0
999
Sec
IS-S
PA09
Set the activation delay of compressor’s
thermal alarm
0
0
999
Sec
IS-S
PA10
Set the activation delay of common
diffrerential oil alarm and for compressors
10
0
999
Sec
IS-S
PA11
Set the rearmament type for high pressure
discharging alarm
M
A (0)
M (1)
-
IS-S
PA12
Set the rearmament type for compressor’s
thermal alarm
M
A (0)
M (1)
-
IS-S
PA14
Set the rearmament type for compressor’s
differential oil
M
A (0)
M (1)
-
IS-S
PA15
Set the setpoint for low pressure alarm over
suction probe of circuit 1
0.5
PH01
PA17
Bar
IS-S
PA16
Set the differntial for low pressure alarm
over suction probe of circuit 1
0.5
0.0
20.0
Bar
IS-S