C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL

Page 39

5: R410A
6: R507

PH32

Set the unit of measurement of temperature:
0: °Celsius
1: °Fahrenheit

0 (°C)

0

1

-

IS-V

PH33

Set the unit of measurement of pressure:
0: Bar
1: psi

0 (Bar)

0

1

-

IS-V

PH35

Enable load losses compensation on suction
line (neutral zone)
0: NO
1: YES

0 (NO)

0

1

-

IS-V

PH36

Load losses compensation factor

0.2

0.1

5.0

Bar

IS-V

PH40

Set the display in pressure or temperature
0: Pressure
1: Temperature

0

0

1

-

IS-V

PH43

Set the type of A/3 universal analogue input
2: NTC
3: 0-20mA
4: 4-20mA
5: reserved

4

4-20mA

2

5

-

IS-V

PH44

Set the type of A/4 universal analogue
2: NTC
3: 0-20mA
4: 4-20mA
5: reserved

4

4-20mA

2

5

-

IS-V

PH50

Set the display with the icons only
0: NO
1: YES

1 (SI)

0

1

-

IS-V

PH51

Set the display of numeric icons
0: NO
1: YES

1 (SI)

0

1

-

IS-V

PH52

Set the display of Evco icon
0: NO
1: YES

1 (SI)

0

1

-

IS-V

PA01

Enable the alarm of compressors’ operation
hours

No

No (0)

Si (1)

-

IS-S

PA02

Enable the alarm of fans’ operation hours

No

No (0)

Si (1)

-

IS-S

PA03

Set the activation delay of high pressure
suction alarms

1

0

999

Sec

IS-S

PA04

Set the detection delay of expansion alarm

5

0

999

Sec

IS-S

PA05

Set the activation delay of liquid level alarm

90

0

999

Sec

IS-S

PA06

Set the detection delay of the alarms over
suction and discharging probes

5

0

240

Sec

IS-S

PA07

Set the activation delay of low pressure
discharging alarm

30

0

999

Sec

IS-S

PA08

Set the activation delay of low pressure
suction alarms

30

0

999

Sec

IS-S

PA09

Set the activation delay of compressor’s
thermal alarm

0

0

999

Sec

IS-S

PA10

Set the activation delay of common
diffrerential oil alarm and for compressors

10

0

999

Sec

IS-S

PA11

Set the rearmament type for high pressure
discharging alarm

M

A (0)

M (1)

-

IS-S

PA12

Set the rearmament type for compressor’s
thermal alarm

M

A (0)

M (1)

-

IS-S

PA14

Set the rearmament type for compressor’s
differential oil

M

A (0)

M (1)

-

IS-S

PA15

Set the setpoint for low pressure alarm over
suction probe of circuit 1

0.5

PH01

PA17

Bar

IS-S

PA16

Set the differntial for low pressure alarm
over suction probe of circuit 1

0.5

0.0

20.0

Bar

IS-S