C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL

Page 37

PC71

Set compressors’ throttlings pressure
(circuit 1)

22.0

PH03

PH04

Bar

IS-C

PC72

Set compressors’ throttlings pressure
(circuit 2)

22.0

PH03

PH04

Bar

IS-C

Visible if

PG01 > 1

PC74

Differential of compressors’ throttlings
pressure

4.0

0.1

10.0

Bar

IS-C

PC75

Minimum time for compressors’ throttlings
maintenance

2

0

999

Min

IS-C

PC76

Throttling percentage value

50

0

100

%

IS-C

PC78

Compressors’ sideband steps overlapping
factor (sideband)

0

0

100

%

IS-C

PC81

Power supplied by compressor 1

0

0

1000

kW

IS-C

Visibile if

PG03 = 1

and

visibility

*1

PC82

Power supplied by compressor 2

0

0

1000

kW

IS-C

Visibile if

PG03 = 1

and

visibility

*1

PC83

Power supplied by compressor 3

0

0

1000

kW

IS-C

Visibile if

PG03 = 1

and

visibility

*1

PC84

Power supplied by compressor 4

0

0

1000

kW

IS-C

Visibile if

PG03 = 1

and

visibility

*1

PF01

Rotation used for fans management:
0: FIFO
1: LIFO
2: FIFO + hours of operation
3: LIFO + hours of operation

0 = FIFO

0

3

n

IS-F

PF02

Set if fans regulation happens only if at least
one compressor is switched on on

0 = No

0

1

-

IS-F

PF07

Minimum time that must elapse between the
switching on of two different fans

2

0

999

Sec

IS-F

PF08

Minimum time that must elapse between the
switching off of two different fans

2

0

999

Sec

IS-F

PF11

Number of fans that will be forced if there
is an alarm over the discharging probe of
circuit 1 .

1

0

PG41

N

IS-F

PF31

Number of fans that will be forced if there
is an alarm over the discharging probe of
circuit 2.

1

0

PG45

N

IS-F

Visible if

PG01 > 1

and

PG30 = 0

PF71

Enable floating condensation

0 = No

0

1

-

IS-F

PF72

Delta of condensation temperature

0.0

-20.0

20.0

°C

IS-F

PF73

Minimum limit of consensation setpoint

30.0

10.0

PF74

°C

IS-F

PF74

Maximum limit of consensation setpoint

40.0

PF73

45.0

°C

IS-F

PF78

Fans’ sideband steps overlapping factor
(sideband)

0

0

100

%

IS-F

PH01

Set the minimum value of steps-bottom for
the suction probe

-0.5

-10.0

PH02

Bar

IS-V

PH02

Set the maximum value of steps-bottom for
the suction probe

7.0

PH01

45.0

Bar

IS-V

PH03

Set the maximum value of steps-bottom for
the discharging probe

0.0

-10.0

PH04

Bar

IS-V

PH04

Set the maximum value of steps-bottom for
the discharging probe

30.0

PH03

45.0

Bar

IS-V