EVCO c-pro nano RACK User Manual
Page 37

C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL
Page 37
PC71
Set compressors’ throttlings pressure
(circuit 1)
22.0
PH03
PH04
Bar
IS-C
PC72
Set compressors’ throttlings pressure
(circuit 2)
22.0
PH03
PH04
Bar
IS-C
Visible if
PG01 > 1
PC74
Differential of compressors’ throttlings
pressure
4.0
0.1
10.0
Bar
IS-C
PC75
Minimum time for compressors’ throttlings
maintenance
2
0
999
Min
IS-C
PC76
Throttling percentage value
50
0
100
%
IS-C
PC78
Compressors’ sideband steps overlapping
factor (sideband)
0
0
100
%
IS-C
PC81
Power supplied by compressor 1
0
0
1000
kW
IS-C
Visibile if
PG03 = 1
and
visibility
*1
PC82
Power supplied by compressor 2
0
0
1000
kW
IS-C
Visibile if
PG03 = 1
and
visibility
*1
PC83
Power supplied by compressor 3
0
0
1000
kW
IS-C
Visibile if
PG03 = 1
and
visibility
*1
PC84
Power supplied by compressor 4
0
0
1000
kW
IS-C
Visibile if
PG03 = 1
and
visibility
*1
PF01
Rotation used for fans management:
0: FIFO
1: LIFO
2: FIFO + hours of operation
3: LIFO + hours of operation
0 = FIFO
0
3
n
IS-F
PF02
Set if fans regulation happens only if at least
one compressor is switched on on
0 = No
0
1
-
IS-F
PF07
Minimum time that must elapse between the
switching on of two different fans
2
0
999
Sec
IS-F
PF08
Minimum time that must elapse between the
switching off of two different fans
2
0
999
Sec
IS-F
PF11
Number of fans that will be forced if there
is an alarm over the discharging probe of
circuit 1 .
1
0
PG41
N
IS-F
PF31
Number of fans that will be forced if there
is an alarm over the discharging probe of
circuit 2.
1
0
PG45
N
IS-F
Visible if
PG01 > 1
and
PG30 = 0
PF71
Enable floating condensation
0 = No
0
1
-
IS-F
PF72
Delta of condensation temperature
0.0
-20.0
20.0
°C
IS-F
PF73
Minimum limit of consensation setpoint
30.0
10.0
PF74
°C
IS-F
PF74
Maximum limit of consensation setpoint
40.0
PF73
45.0
°C
IS-F
PF78
Fans’ sideband steps overlapping factor
(sideband)
0
0
100
%
IS-F
PH01
Set the minimum value of steps-bottom for
the suction probe
-0.5
-10.0
PH02
Bar
IS-V
PH02
Set the maximum value of steps-bottom for
the suction probe
7.0
PH01
45.0
Bar
IS-V
PH03
Set the maximum value of steps-bottom for
the discharging probe
0.0
-10.0
PH04
Bar
IS-V
PH04
Set the maximum value of steps-bottom for
the discharging probe
30.0
PH03
45.0
Bar
IS-V