C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL

Page 34

PC27

SpeedUp time for the inverter of circuit 1
compressors

0

0

999

Sec

IS-R1

Visibile if

PG12 = 1

PC28

Time within which the inverter changes
from minimum value to its maximum value
for the neutral zone adjustments of circuit 1
compressors

10

0

999

Sec

IS-R1

Visibile if

PG12 = 1

PF12

Minimum value of discharging setpoint of
circuit 1 fans

1.0

PH03

SPF1

Bar

IS-R1

PF13

Maximum value of discharging setpoint of
circuit 1 fans

25.0

SPF1

PH04

Bar

IS-R1

PF14

Set the regulation type for management of
circuit 1 fans

Sideband(

0)

Sideban

d (0)

Neutal

zone(1)

-

IS-R1

PF16

Integral time of the sideband adjustment of
circuit 1 fans

600

0

999

Sec

IS-R1

Visibile if

PF14 = 0

PF17

Proportional band for the sideband
adjustment of circuit 1 fans

0.5

0

20.0

Bar

IS-R1

Visibile if

PF14 = 0

PF18

Value of the Zone for neutral zone
adjustment of circuit 1 fans

1.0

0

20.0

Bar

IS-R1

Visibile if

PF14 = 1

PF20

Insertion / release time for the next fan in
neutral zone adjustment

10

0

999

Sec

IS-R1

Visibile if

PF14 = 1

PF24

Differential for the inverter adjustment of
circuit 1 fans

0.5

0.0

20.0

Bar

IS-R1

Visibile if

PG42 = 1

PF25

Offset in relation to the suction setpoint for
inverter adjustment of circuit 1 fans

0.0

-20.0

20.0

Bar

IS-R1

Visibile if

PG42 = 1

PF26

Minimum value of the inverter of circuit 1
fans

0.0

0.0

100.0

%

IS-R1

Visibile if

PG42 = 1

PF27

SpeedUp time for the inverter of circuit 1
fans

2

0

999

Sec

IS-R1

Visibile if

PG42 = 1

PF28

Time within which the inverter changes
from minimum value to its maximum value
for the neutral zone adjustments of circuit 1
fans

10

0

999

Sec

IS-R1

Visibile if

PG42 = 1

PC32

Minimum value of suction setpoint of
circuit 2 fans

0.1

PH01

SPC2

Bar

IS-R2

Visible if

PG01 > 1

PC33

Maximum value of suction setpoint of
circuit 2 fans

2.5

SPC2

PH02

Bar

IS-R2

Visible if

PG01 > 1

PC34

It sets the regulation type for management
of circuit 2 compressors

Neutral

zone (1)

Sideban

de (0)

Neutral

zone (1)

-

IS-R2

Visible if

PG01 > 1

PC36

IT integral time of the sideband adjustment
of circuit 2 compressors

600

0

999

Sec

IS-R2

Visible if

PG01 > 1

and

PC34 = 0

PC37

PB proportional band for the sideband
adjustment of circuit 2 compressors

0.5

0

20.0

Bar

IS-R2

Visible if

PG01 > 1

and

PC34 = 0

PC38

Value of the Zone for neutral zone
adjustment of circuit 2 compressors

0.5

0

20.0

Bar

IS-R2

Visible if

PG01 > 1

and

PC34 = 1

PC39

Differential for the neutral zone adjustment
of circuit 2, within which the calculation for
switching on/off of a further step varies

0.5

0

20.0

Bar

IS-R2

Visible if

PG01 > 1

and

PC34 = 1

PC40

Minimum time of insertion for the further
step of circuit 2 compressors (Neutral zone)

20

0

999

Sec

IS-R2

Visible if

PG01 > 1

and

PC34 = 1

PC41

Maximum time of insertion for the further
step of circuit 2 compressors (Neutral zone)

60

0

999

Sec

IS-R2

Visible if

PG01 > 1

and

PC34 = 1

PC42

Minimum time of release for the further

10

0

999

Sec

IS-R2

Visible if