EVCO c-pro nano RACK User Manual
Page 43

C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL
Page 43
associated with the alarm signals of circuit 1
is enabled)
HA21
Set the position of the digital output
associated with the alarm signals of circuit 1
0
0
6 (12)
n
CO-Hw
Visibile if
PG01 > 1
Hd01
Set the position of the digital input for the
Global On/Off Switch
0
0
5(10)
n
CO-Hw
(10 if
expansion
is enabled)
Hd02
Set the position of the digital input relative
to the secondary setpoint for the
management of the compressors
0
0
5(10)
n
CO-Hw
(10 if
expansion
is enabled)
Hd03
Set the position of the digital input relative
to the secondary setpoint for the
management of the fans
0
0
5(10)
n
CO-Hw
(10 if
expansion
is enabled)
Hd11
Set the position of the digital input for the
On/Off Switch for Circuit 1
0
0
5(10)
n
CO-Hw
(10 if
expansion
is
enabled))
Hd12
Set the position of the digital input
associated with the liquid level alarm of
circuit 1
0
0
5(10)
n
CO-Hw
(10 if
expansion
is enabled)
Hd13
Set the position of the digital input
associated with the low pressure alarm on
the suction pressure regulator of circuit 1
0
0
5(10)
n
CO-Hw
(10 if
expansion
is enabled)
Hd14
Set the position of the digital input
associated with the high pressure alarm on
the discharge pressure regulator of circuit 1
5
0
5(10)
n
CO-Hw
(10 if
expansion
is enabled)
Hd15
Set the position of the digital input
associated with the oil differential alarm for
compressors of circuit 1
0
0
5(10)
n
CO-Hw
(10 if
expansion
is enabled)
Hd16
Set the position of the digital input
associated with the common thermal alarm
for the fans of circuit 1
0
0
5(10)
n
CO-Hw
(10 if
expansion
is enabled)
Hd21
Set the position of the digital input for the
On/Off Switch for Circuit 2
0
0
5(10)
n
CO-Hw
(10 if
expansion
is
enabled);
visibile if
PG01 > 1
Hd22
Set the position of the digital input
associated with the liquid level alarm of
circuit 2
0
0
5(10)
n
CO-Hw
(10 if
expansion
is
enabled);
visibile if
PG01 > 1
Hd23
Set the position of the digital input
associated with the low pressure alarm on
the suction pressure regulator of circuit 2
0
0
5(10)
n
CO-Hw
(10 if
expansion
is
enabled);