C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL

Page 43

associated with the alarm signals of circuit 1

is enabled)

HA21


Set the position of the digital output
associated with the alarm signals of circuit 1

0

0

6 (12)

n

CO-Hw

Visibile if

PG01 > 1

Hd01

Set the position of the digital input for the
Global On/Off Switch

0

0

5(10)

n

CO-Hw

(10 if

expansion

is enabled)

Hd02


Set the position of the digital input relative
to the secondary setpoint for the
management of the compressors

0

0

5(10)

n

CO-Hw

(10 if

expansion

is enabled)

Hd03

Set the position of the digital input relative
to the secondary setpoint for the
management of the fans

0

0

5(10)

n

CO-Hw

(10 if

expansion

is enabled)

Hd11


Set the position of the digital input for the
On/Off Switch for Circuit 1

0

0

5(10)

n

CO-Hw

(10 if

expansion

is

enabled))

Hd12


Set the position of the digital input
associated with the liquid level alarm of
circuit 1

0

0

5(10)

n

CO-Hw

(10 if

expansion

is enabled)

Hd13


Set the position of the digital input
associated with the low pressure alarm on
the suction pressure regulator of circuit 1

0

0

5(10)

n

CO-Hw

(10 if

expansion

is enabled)

Hd14


Set the position of the digital input
associated with the high pressure alarm on
the discharge pressure regulator of circuit 1

5

0

5(10)

n

CO-Hw

(10 if

expansion

is enabled)

Hd15


Set the position of the digital input
associated with the oil differential alarm for
compressors of circuit 1

0

0

5(10)

n

CO-Hw

(10 if

expansion

is enabled)

Hd16


Set the position of the digital input
associated with the common thermal alarm
for the fans of circuit 1

0

0

5(10)

n

CO-Hw

(10 if

expansion

is enabled)

Hd21


Set the position of the digital input for the
On/Off Switch for Circuit 2

0

0

5(10)

n

CO-Hw

(10 if

expansion

is

enabled);

visibile if
PG01 > 1

Hd22


Set the position of the digital input
associated with the liquid level alarm of
circuit 2

0

0

5(10)

n

CO-Hw

(10 if

expansion

is

enabled);

visibile if
PG01 > 1

Hd23


Set the position of the digital input
associated with the low pressure alarm on
the suction pressure regulator of circuit 2

0

0

5(10)

n

CO-Hw

(10 if

expansion

is

enabled);