EVCO c-pro nano RACK User Manual
Page 38

C-PRO NANO RACK E C-PRO MICRO RACK APPLICATION MANUAL
Page 38
PH05
Enable the machine switching on/off
pressing ESC/Stand- by key
Si
No (0)
Si (1)
-
IS-V
PH07
Enable the machine switching on/off from
digital output
No
No (0)
Si (1)
-
IS-V
PH08
Enable the single circuit’s switching on/off
from respective digital output
No
No (0)
Si (1)
-
IS-V
PH09
Enable the machine switching on/off from
supervisor
No
No (0)
Si (1)
-
IS-V
PH10
Enable the single circuits’ switching on/off
by supervisor
No
No (0)
Si (1)
-
IS-V
PH11
Modbus address of the card
1
1
247
n
IS-V
PH12
Baud Rate of communication for the card
(1=2400, 2=4800, 3=9600, 4=19200)
3
1
4
n
IS-V
PH13
ModBu parity (0=none, 1=Odd, 2=Even)
2
0
2
n
IS-V
PH14
StopBit ModBus (0=1bit, 1=2bit)
0
0
1
n
IS-V
PH15
Restore the default of parametes‘ factory
No
No (0)
Si (1)
-
IS-D
(MAP)
Wait that
the value
0 is reread
at the end
of
restoring
PH17
Set the logic of digital inputs used for
alarms management:
0: Normally open NO
1: Normally close NC
NC
NO (0)
NC (1)
-
IS-V
PH18
Set the logic of relays used for alarms
0: Normally openNO
1: Normally close NC
NO
NO (0)
NC (1)
-
IS-V
PH19
Set the logic of digital inputs used for the
management of the following functions:
- OnOff Remote global
- OnOff Remote circuits
- secondary setpoint of compressors
-secondary setpoint of fans
0: Normally open NO
1: Normally closet NC
NO
NO (0)
NC (1)
-
IS-V
PH20
Compressors inverter consent digital output
command logic
=0: Energized contact-100% consent
enabled
=1: Energized contact-100% consent
disabled
0
0
1
-
IS-V
PH21
Fans inverter consent digital output
command logic
=0: Energized contact-100% consent
enabled
=1: Energized contact-100% consent
disabled
0
0
1
-
IS-V
PH23
Set the habilitation of the probe for
detection of room temperature
0 = No
0
1
-
IS-V
PH24
Set the habilitation of the probe for
detection of external temperature
0 = No
0
1
-
IS-V
PH25
Set the habilitation of secondary setpoint
function by digital input
0 = No
0
1
-
IS-V
PH26
Set the habilitation of secondary setpoint
function by supervisor
0 = No
0
1
-
IS-V
PH31
Set the type of coolant used (temperature-
pressure conversion)
0: No coolant
1: R22
2: R134a
3: R404A
4: R407C
3
R404A
0
6
-
IS-V