Operation Time Log
9.4.2
The Operation Time Log consists of a string of ASCII records stored in non-volatile memory within
the C-More Control Panel. Events such as power-up, ignition and turn-off are time stamped. Data
logged while the unit is running are run-length encoded. Data is logged or the run-length
incremented every 30 seconds. For a new run record to be logged, the fire rate or flame strength
must change by more than 5%, or the run mode must change. At steady-state, the run-length is
allowed to reach a maximum of 30 minutes before the record is logged. This means that no more
than 30 minutes of data can be lost if the unit loses power. Table 9-2 shows a sample Operation
Time Log for a boiler:
The Operation Time Log can only be accessed through the RS232 interface using a laptop or other
terminal device. Ten operation time records are displayed for each T command entry. The operation
time log can be cleared ONLY by factory authorized personnel using the Clear Log option in the
Factory menu.
NOTE:
The Sensor (S) Log can store up to 1200 records. Therefore,
to view the most recently logged record, enter “S” followed by
0 (zero) and then press Enter (i.e. S0
earlier records in reverse chronological order, enter S and
press Enter. To go back 200 or 700 records, enter S200 or
S700, etc. and press Enter.
Sensor Log
9.4.3
The sensor values can be logged at a different rate if needed by setting the Sensor Log Interval in
the Diagnostics Menu. The log interval can vary from once every minute to once every day. Table 9-
3 shows a sample Sensor Log every 5 minutes for a boiler running in Constant Setpoint mode.
Table 9-1. Sample Fault Log Display
No.
Fault Message
Cycle
Date
Time
0 Direct Drive Signal Fault
609 1/10/02 8:42am
1 Low Gas Pressure
366 7/04/01 5:29pm
2 Loss of Power
0 1/01/01 11:50am
Table 9-2. Sample Operation Time Log Display
Status
Fire Rate Flame Run Length
Date
Time
Off, Direct Drive
0
0
8
1/15/02
2:35pm
Run, Direct Drive
38
100
34
1/15/02
2:27pm
Run, Direct Drive
31
100
30
1/15/02
1:53am
Run, Direct Drive
35
100
2
1/15/02
1:23pm
Run, Direct Drive
29
100
0
1/15/02
1:21pm
Ignition
0
0
0
1/15/02
1:20pm
Off, Switch
0
0
35
1/15/02
12:30pm
Run, Manual
40
100
0
1/15/02
11:55am
Ignition
0
0
0
1/15/02
11:55am
Power-up
0
0
0
1/15/02
11:50am