CHAPTER 1: SAFETY PRECAUTIONS

Page

12 of 152 PR2: 05/09/12

Benchmark 1.5LN Low NOx Boiler

Operation and Maintenance Manual

OMM-0041_0D

GF-120

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288

4. INSPECTION. The state or local gas inspector of the side wall horizontally vented

gas fueled equipment shall not approve the installation unless, upon inspection, the

inspector observes carbon monoxide detectors and signage installed in accordance with

the provisions of 248 CMR 5.08(2)(a)1 through 4.

(b) EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:

1. The equipment listed in Chapter 10 entitled "Equipment Not Required To Be Vented"

in the most current edition of NFPA 54 as adopted by the Board; and

2. Product Approved side wall horizontally vented gas fueled equipment installed in a

room or structure separate from the dwelling, building or structure used in whole or in

part for residential purposes.

(c) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM

PROVIDED. When the manufacturer of Product Approved side wall horizontally vented gas

equipment provides a venting system design or venting system components with the equipment,

the instructions provided by the manufacturer for installation of the equipment and the venting

system shall include:

1. Detailed instructions for the installation of the venting system design or the venting

system components; and
2. A complete parts list for the venting system design or venting system.

(d) MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM NOT

PROVIDED. When the manufacturer of a Product Approved side wall horizontally vented gas

fueled equipment does not provide the parts for venting the flue gases, but identifies "special

venting systems", the following requirements shall be satisfied by the manufacturer:

1. The identification of each "special venting system" shall include the listing of either

the website, phone number or manufacturer’s address where the venting system

installation instructions can be obtained, and

2. The "special venting systems" shall be Product Approved by the Board, and the

instructions for that system shall include a parts list and detailed installation instructions.

(e) A copy of all installation instructions for the Product Approved side wall horizontally vented

gas fueled equipment and all the venting instructions, parts lists and/or design instructions for

the venting system shall remain with the appliance or equipment at the completion of the

installation.

_______________ [End of Extracted Information From 248 CMR 5.08 (2)__________________