CHAPTER 6: SAFETY DEVICE TESTING

PR2: 05/09/12 Page

69 of 152

Benchmark 1.5LN Low NOx Boiler

Operation and Maintenance Manual

OMM-0041_0D

GF-120

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288

6.11 IGNITION SWITCH OPEN DURING IGNITION

The Ignition Switch (and the Purge Switch) is located on the Air/Fuel Valve. To check the

switch, proceed as follows:
1. Set the unit’s

ON/OFF switch to the OFF position.

2. Place the unit in Manual Mode and set the valve position between 25% and 30%.
3. Remove the Air/Fuel Valve cover (Figure 6-5) by rotating the cover counterclockwise to

unlock and lift up to remove.

4. Remove one of the two wires (#169 or #170) from the Ignition Switch (Figure 6-6).
5. Initiate a unit start sequence.
6. The unit should begin its start sequence and then shut down and display IGN SWITCH

OPEN DURING IGNITION.

7. Replace the wire on the Ignition Switch and press the

CLEAR button. The unit should

restart.

AIR/FUEL VALVE COVER

(ROTATE CCW TO REMOVE)

Figure 6-5: Air/Fuel Valve Cover Location