beautypg.com

Benchmark 1.5ln low nox boiler, Gf-120 – AERCO BMK 1.5 LN July 2011 User Manual

Page 89

background image

CHAPTER 7: MAINTENANCE

PR2: 05/09/12 Page

89 of 152

Benchmark 1.5LN Low NOx Boiler

Operation and Maintenance Manual

OMM-0041_0D

GF-120

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288

TABLE 8-1. BOILER TROUBLESHOOTING (Continued)

FAULT INDICATION

PROBABLE CAUSES

CORRECTIVE ACTION

IGN BOARD

COMM FAULT

1. Communication fault has occurred

between the PMC board and

Ignition/Stepper (IGST) board

1. Press CLEAR button and restart unit. If fault persists, contact

qualified Service Personnel.

IGN SWTCH CLOSED

DURING PURGE

1. Air/Fuel Valve not rotating

2. Defective or shorted switch

3. Switch wired incorrectly

4. Defective Power Supply Board or

fuse

5. Defective IGST Board

1. Start the unit. The Air/Fuel Valve should rotate to the purge

(open) position. If the valve does not rotate at all or does not

rotate fully open, check the Air/Fuel Valve calibration. If

calibration is okay, the problem may be in the Air-Fuel Valve or

the Control Box. Refer to qualified service personnel

2. . If the Air/Fuel Valve does rotate to purge, check the ignition

switch for continuity between the N.O. and COM terminals. If the

switch shows continuity when not in contact with the cam replace

the switch.

3. Check to ensure that the switch is wired correctly (correct wire

numbers on the normally open terminals). If the switch is wired

correctly, replace the switch

4. Check DS1 & DS2 LEDs on Power Supply Board. If they are not

steady ON, replace Power Supply Board.

5. Check “Heartbeat” LED DS1 and verify it is blinking ON & OFF

every second. If not, replace IGST Board.

IGN SWTCH OPEN

DURING IGNITION

1. Air/Fuel Valve not rotating to

ignition position.

2. Defective ignition switch

3. Defective Power Supply Board or

fuse

4. Defective IGST Board

1. Start the unit. The Air/Fuel Valve should rotate to the purge

(open) position, then back to ignition position (towards closed)

during the ignition cycle. If the valve does not rotate back to the

ignition position, check the Air/Fuel Valve calibration. If

calibration is okay, the problem may be in the Air/Fuel Valve or

the Control Box. Refer fault to qualified service personnel.

2. If the Air/Fuel Valve does rotate to the ignition position, check the

ignition position switch for continuity between the N.O. and COM

terminals when in contact with the cam.

3. Check DS1 & DS2 LEDs on Power Supply Board. If they are not

steady ON, replace Power Supply Board.

4. Check “Heartbeat” LED DS1 and verify it is blinking ON & OFF

every second. If not, replace IGST Board.