beautypg.com

4 low water level fault test, 5 water temperature fault test, Benchmark 1.5ln low nox boiler – AERCO BMK 1.5 LN July 2011 User Manual

Page 63: Gf-120

background image

CHAPTER 6: SAFETY DEVICE TESTING

PR2: 05/09/12 Page

63 of 152

Benchmark 1.5LN Low NOx Boiler

Operation and Maintenance Manual

OMM-0041_0D

GF-120

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288

6. The unit should shut down and display a HIGH GAS PRESSURE fault message when the

gas pressure exceeds 4.7” W.C. The

FAULT indicator should also start flashing.

7. Reduce the gas pressure back to 3.0” W.C.
8. Press the

CLEAR button on the Control Box to clear the fault.

9. The fault message should clear and the

FAULT indicator should go off. The unit should

restart.

10.

Upon test completion, close the ball valve and remove the manometer. Replace the

1/4“ plug removed in step 1.

6.4 LOW WATER LEVEL FAULT TEST

To simulate a low water level fault:
1. Set the

ON/OFF switch to the OFF position

2. Close the water shut-off valves in the supply and return piping to the unit.
3. Slowly open the drain valve on the rear of the unit. If necessary the unit’s relief valve may

be opened to aid in draining.

4. Continue draining the unit until a LOW WATER LEVEL fault message is displayed and the

FAULT indicator flashes.

5. Place the unit in the Manual Mode and raise the valve position above 30%.
6. Set the

ON/OFF switch to the ON position. The READY light should remain off and the unit

should not start. If the unit does start, shut the unit off immediately and refer fault to

qualified service personnel.

7. Close the drain and pressure relief valve used in draining the unit.
8. Open the water shut-off valve in the return piping to the unit.
9. Open the water supply shut-off valve to the unit to refill.
10. After the shell is full, press the

LOW WATER LEVEL RESET button to reset the low water

cutoff.

11. Press the

CLEAR button to reset the FAULT LED and clear the displayed error message.

12. Set the

ON/OFF switch to the ON position. The unit is now ready for operation.

6.5 WATER TEMPERATURE FAULT TEST

A high water temperature fault is simulated by adjusting the automatic over-temperature switch.

This switch is accessible from the front of the unit as shown in Figure 6-2.
1. Start the unit in the normal operating mode. Allow the unit to stabilize at its setpoint.
2. Lower the adjustable over-temperature switch setting to match the displayed OUTLET

TEMPERATURE.

3. Once the adjustable over-temperature switch setting is approximately at, or just below, the

actual outlet water temperature, the unit should shut down. The

FAULT indicator should

start flashing and a HIGH WATER TEMP SWITCH OPEN fault message should be

displayed. It should not be possible to restart the unit.

4. Reset the adjustable over-temperature switch to its original setting.