CHAPTER 2: INSTALLATION

Page

18 of 152 PR2: 05/09/12

Benchmark 1.5LN Low NOx Boiler

Operation and Maintenance Manual

OMM-0041_0D

GF-120

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288

NOTE

All gas piping must be arranged so that it does not interfere with

removal of any covers, inhibit service/maintenance, or restrict

access between the unit and walls, or another unit.

A 1-1/2 inch gas inlet connection is located on the rear of the unit as shown in Figure 2-3.
Prior to installation, all pipes should be de-burred and internally cleared of any scale, metal

chips or other foreign particles. Do Not install any flexible connectors or unapproved gas

fittings. Piping must be supported from the floor, ceiling or walls only and must not be supported

by the unit.
A suitable piping compound, approved for use with natural gas, should be used. Any excess

must be wiped off to prevent clogging of components.
To avoid unit damage when pressure testing gas piping, isolate the unit from the gas supply

piping. At no time should the gas pressure applied to the unit exceed 14” W.C. Leak test all

external piping thoroughly using a soap and water solution or suitable equivalent. The gas

piping used must meet all applicable codes.

Gas Supply Specifications.

2.7.1

The gas supply input specifications to the unit for Natural Gas are as follows:

The maximum static pressure to the unit must not exceed 14” W.C. The gas supply pressure to

the unit must be of sufficient capacity to provide 1500 cfh while maintaining the gas pressure at

4.0 inches W.C. for FM, or 4.2 inches W.C. for IRI gas trains.

Manual Gas Shutoff Valve

2.7.2

A manual shut-off valve must be installed in the gas supply line upstream of the Boiler as shown

in Figure 2-6. Maximum allowable gas pressure to the Boiler is 14” W.C.

NOTE

Paragraph 2.7.3 applies only to bolier installations within the

Commonwealth of Massachusetts.

External Gas Supply Regulator

2.7.3

For Massachusetts installations, a mandatory external gas supply regulator must be positioned

as shown in Figure 2-6. The gas supply regulator must be properly vented to outdoors. Consult

the local gas utility for detailed requirements concerning venting of the the supply gas regulator.

NOTE

The external regulator must be capable of regulating 1,500,000

BTU/HR of natural gas while maintaining a gas pressure of 4.0”

W.C. to the boiler.

CAUTION

A lock-up style regulator MUST be used when gas supply

pressure will exceed 14” W.C.