TABLE 8-1. BOILER TROUBLESHOOTING

FAULT

INDICATION

PROBABLE CAUSES

CORRECTIVE ACTION

AIRFLOW FAULT

DURING IGNITION

1. Blower stopped running due to thermal or

current overload

2. Blocked Blower inlet or inlet ductwork
3. Blocked Blower proof switch

4. Blocked blocked-air inlet switch

5. Defective Blower proof switch


6. Defective blocked-air inlet switch


7. Loose temperature to AUX connection in I/O

Box

8. Defective temperature sensor

9. Loose wire connection between the 0-10V

signal from I/O box to the Blower Motor

input.

10. Defective I/O box

11. Wrong 0-10V output selection on the

control box

12. Defective Air-Fuel Valve potentiometer

1. Check combustion blower for signs of excessive heat or high

current drain that may trip thermal or current overload devices.

2. Inspect the inlet to the combustion blower including any ductwork

leading up to the combustion blower for signs of blockage.

3. Remove the Blower proof switch and inspect for signs of blockage,

clean or replace as necessary.

4. Remove the blocked-air inlet switch and inspect for signs of

blockage, clean or replace as necessary.

5. Measure the Blower proof switch for continuity with the

combustion blower running. If there is an erratic resistance reading

or the resistance reading is greater than zero ohms, replace the

switch.

6. Measure the blocked-air inlet switch for continuity with the

combustion blower running. If there is an erratic resistance reading

or the resistance reading is greater than zero ohms, replace the

switch.

7. Check the actual inlet air temperature and measure voltage at

AUX input in the I/O Box. Verify that the voltage conforms to the

values shown in the tabular listing provided in Appendix C.

8. Refer to CORRECTIVE ACTION 7 and verify that the voltage

conforms to the values shown in Appendix C.

9. Check wire connection from I/O Box 0-10V signal to the Blower

Motor.

10. Measure voltage at the I/O box 0-10V output. A voltage of 8.2V

equates to a 100% open valve position.

11. Check the Analog Out option on the C-More Configuration Menu.

Valve Position 0-10V should be selected.

12. Check Air/Fuel Valve position at 0%, 50% and 100% open

positions. The positions on the VALVE POSITION bargraph

should match the dial readings on the Air/Fuel Valve dial.