beautypg.com

12 fault relay (13), 11 auxiliary relay contacts (14), 12 flue gas vent installation – AERCO BMK 1.5 LN July 2011 User Manual

Page 26: 13 combustion air, Benchmark 1.5ln low nox boiler, Gf-120

background image

CHAPTER 2: INSTALLATION

Page

26 of 152 PR2: 05/09/12

Benchmark 1.5LN Low NOx Boiler

Operation and Maintenance Manual

OMM-0041_0D

GF-120

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288

from 0 to 120 seconds. This option is locate in the Configuration Menu (Chapter 3, Table 3-4).

FAULT RELAY (13)

2.10.12

The fault relay is a single pole double throw (SPDT) relay having a normally open and normally

closed set of relay contacts that are rated for 5 amps at 120 VAC and 5 amps at 30 VDC. The

relay energizes when any fault condition occurs and remains energized until the fault is cleared

and the CLEAR button is depressed. The fault relay connections are shown in Figure 2-10.

2.11 AUXILIARY RELAY CONTACTS (14)

Each Boiler is equipped with a single pole double throw (SPDT) relay that is energized when

there is a demand for heat and de-energized after the demand for heat is satisfied. The relay is

provided for the control of auxiliary equipment, such as pumps and louvers, or can be used as a

Boiler status indictor (firing or not firing). Its contacts are rated for 120 VAC @ 5 amps. Refer to

Figure 2-10 to locate the AUX RELAY terminals for wiring connections.

2.12 FLUE GAS VENT INSTALLATION

The minimum allowable vent diameter for a single Benchmark 1.5 Boiler is 6

inches.

The AERCO Benchmark Venting and Combustion Air Guide, GF-2050, must be consulted

before any flue gas vent or inlet air venting is designed or installed. U/L listed, positive pressure,

watertight vent materials as specified in AERCO’s GF-2050, must be used for safety and code

compliance. Since the unit is capable of discharging low temperature exhaust gases, horizontal

sections of the flue vent system must be pitched back to the unit a minimum of 1/4 inch per foot

to avoid condensate pooling and allow for proper drainage.
The combined pressure drop of vent and combustion air systems must not exceed 140

equivalent feet of 6 inch ducting. Fittings as well as pipe lengths must be calculated as part of

the equivalent length.
For a natural draft installation the draft must not exceed ±0.25 inch W.C. These factors must be

planned into the vent installation. If the maximum allowable equivalent lengths of piping are

exceeded, the unit will not operate properly or reliably.
For Massachusetts boiler installations, the Heatfab Division of the Selkirk Corporation provides

vent systems which conform to all applicable requirements within the Commonwealth of

Massachusetts. Contact information for this supplier is as follows:

Selkirk Corporation

Heatfab Division (

www.heat-fab.com

)

130 Industrial Blvd.

Turners Falls, MA 01376

Phone: 1-800-772-0739

2.13 COMBUSTION AIR

The AERCO Benchmark Venting and Combustion Air Guide, GF-2050 MUST be consulted

before any flue or combustion supply air venting is designed or implemented. Combustion air

supply is a direct requirement of ANSI 223.1, NFPA-54, CSA B149.1 and local codes. These

codes should be consulted before a permanent design is determined.
The combustion air must be free of chlorine, halogenated hydrocarbons, or other chemicals that

can become hazardous when used in gas-fired equipment. Common sources of these

compounds are swimming pools, degreasing compounds, plastic processing and refrigerants.

Whenever the environment contains these types of chemicals, combustion air must be supplied

from a clean area outdoors for the protection and longevity of the equipment.