CHAPTER 7: MAINTENANCE

PR2: 05/09/12 Page

87 of 152

Benchmark 1.5LN Low NOx Boiler

Operation and Maintenance Manual

OMM-0041_0D

GF-120

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288

TABLE 8-1. BOILER TROUBLESHOOTING (Continued)

FAULT INDICATION

PROBABLE CAUSES

CORRECTIVE ACTION

FLAME LOSS

DURING IGN

(continued)

9. Unstable gas pressure.

10. Carbon or other debris on Burner.

11. Staged ignition solenoid valves

don’t open.

12. Clogged staged ignition piece.

9. Refer to “Gas Pressure Requirements” section of GF-2030:

BMK Gas Supply Design Guide.

10. Remove the burner and inspect for any carbon or debris.

Clean and reinstall.

11. When boiler goes to ignition, listen to the solenoid valves for

a clicking sound to ensure they are opening.

12. Remove and inspect staged ignition piece for blockage.

FLAME LOSS

DURING RUN

1. Worn Flame Detector or cracked

ceramic.

2. Defective Regulator.

3. Poor combustion calibration.
4. Debris on burner.

5. Blocked condensate drain.

1. Remove and inspect the Flame Detector for signs of wear or

cracked ceramic. Replace if necessary.

2. Check gas pressure readings using a gauge or manometer into

and out of the Air/Fuel Valve to ensure that the gas pressure

into and out of the valve is correct.

3. Check combustion calibration. Adjust as necessary.
4. Remove the burner and inspect for any carbon or debris. Clean

and reinstall.

5. Remove blockage in condensate drain.

HEAT DEMAND

FAILURE

1. The Heat Demand Relays on the

Ignition/Stepper board failed to

activate when commanded.

2. Relay is activated when not in

Demand

1. Press CLEAR button and restart the unit. If the fault persists,

replace Ignition/Stepper (IGST) Board.


2. Defective relay. Replace IGST Board.

HIGH EXHAUST

TEMPERATURE

1. Defective exhaust sensor.

2. Carboned heat exchanger due to

incorrect combustion calibration

1. Measure the actual exhaust temperature and continuity of the

exhaust sensor. If the exhaust temperature is less than 475

o

F and the exhaust sensor shows continuity replace the

sensor.

2. If exhaust temperature is greater than 500

o

F, check

combustion calibration. Calibrate or repair as necessary.