beautypg.com

Benchmark 1.5ln low nox boiler, Gf-120 – AERCO BMK 1.5 LN July 2011 User Manual

Page 88

background image

CHAPTER 7: MAINTENANCE

Page

88 of 152 PR2: 05/09/12

Benchmark 1.5LN Low NOx Boiler

Operation and Maintenance Manual

OMM-0041_0D

GF-120

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288

TABLE 8-1. BOILER TROUBLESHOOTING (Continued)

FAULT

INDICATION

PROBABLE CAUSES

CORRECTIVE ACTION

HIGH GAS

PRESSURE

1. Incorrect supply gas pressure.

2. Defective SSOV Actuator.

3. Defective High Gas Pressure Switch

4. Gas pressure snubber not installed.

1. Check to ensure gas pressure at inlet of SSOV is 2 psig maximum.
2. If gas supply pressure downstream of SSOV Actuator cannot be

lowered, to 1.5” W.C. using the gas pressure adjustment screw

(see para. 4.3, step 10), the SSOV Actuator may be defective.

3. Remove the leads from the high gas pressure switch and measure

continuity across the common and normally closed terminals with

the unit not firing. Replace the switch if it does not show continuity.

4. See Figure 8-1. Ensure that the gas pressure snubber is installed

at the high gas pressure switch.

HIGH WATER

TEMP

SWITCH OPEN

1. Faulty Water temperature switch.

2. Incorrect PID settings.

3. Faulty shell temperature sensor.

4. Unit in Manual mode
5. Unit setpoint is greater than Over Temperature

Switch setpoint.

6. Boiler Management System PID or other

settings not correctly setup.

7. No interlock to boiler or BMS to disable

boiler(s) in event that system pumps have

failed.

8. System flow rate changes are occurring faster

than boilers can respond.

1. Test the temperature switch to insure it trips at its actual water

temperature setting.

2. Check PID settings against Menu Default settings in the Appendix.

If the settings have been changed, record the current readings then

reset them to the default values.

3. Using the resistance charts in the Appendix C, Measure the

resistance of Shell sensor and BTU sensor at a known water

temperature.

4. If unit is in Manual Mode switch to Auto Mode.
5. Check setpoint of unit and setpoint of Temperature Switch; Ensure

that the temperature switch is set higher than the unit’s setpoint.

6. Check the BMS for changes to PID default values, correct as

necessary.

7. If system pump is controlled by Energy Management System other

than BMS or pumps are individually controlled by boiler, check to

see if there are flow switches interlocked to the BMS or boiler.

8. If the system is a variable flow system, monitor system flow

changes to ensure that the rate of flow change is not faster than

what the boilers can respond to.

HIGH WATER

TEMPERATURE

1. See HIGH WATER TEMPERATURE SWITCH OPEN.
2. Temp HI Limit setting is too low.

1. See HIGH WATER TEMPERATURE SWITCH OPEN.
2. Check Temp HI Limit setting.