beautypg.com

Chapter 8: troubleshooting guide, 1 introduction, Benchmark 1.5ln low nox boiler – AERCO BMK 1.5 LN July 2011 User Manual

Page 83: Gf-120

background image

PR2: 05/01/11 Page

83 of 152

Benchmark 1.5LN Low NOx Boiler

Operation and Maintenance Manual

OMM-0041_0D

GF-120

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288

CHAPTER 8: TROUBLESHOOTING GUIDE

8.1 INTRODUCTION

This troubleshooting guide is intended to aid service/maintenance personnel in isolating the

cause of a fault in a Benchmark 1.5 Boiler. The troubleshooting procedures contained herein

are presented in tabular form on the following pages. These tables are comprised of three

columns labeled: Fault Indication, Probable Cause and Corrective Action. The numbered items

in the Probable Cause and Corrective Action columns correspond to each other. For example,

Probable Cause No. 1 corresponds to Corrective Action No. 1, etc.

NOTE

The front panel of the C-More Control Box contains an RS232 port

which can be interfaced to a laptop computer or other suitable

device. This RS232 communication feature permits service

personnel to view menu items and data logs which can be useful

in isolating faults. Refer to Chapter 9 of this manual for detailed

RS232 communication set-up and procedures.

When a fault occurs in the Benchmark Boiler, proceed as follows to isolate and correct the fault:

1.

Observe the fault messages displayed in the Control Box display.

2.

Refer to the Fault Indication column in Troubleshooting Table 8-1 which follows and locate

the Fault that best describes the existing conditions.

3.

Proceed to the Probable Cause column and start with the first item (1) listed for the Fault

Indication.

4.

Perform the checks and procedures listed in the Corrective Action column for the first

Probable Cause candidate.

5.

Continue checking each additional Probable Cause for the existing fault until the fault is

corrected.

6.

Paragraph 8.2 and Table 8-2 contain additional troubleshooting information which may apply

when no fault message is displayed.

7. If the fault cannot be corrected using the information provided in the Troubleshooting

Tables, contact your local AERCO Representative.