Benchmark 1.5ln low nox boiler, Gf-120, Aerco – AERCO BMK 1.5 LN July 2011 User Manual
Page 136: Operation and maintenance manual, Appendix g: piping drawings, Legend
APPENDIX G: PIPING DRAWINGS
Page
136 of 152 PR2: 05/09/12
Benchmark 1.5LN Low NOx Boiler
Operation and Maintenance Manual
OMM-0041_0D
GF-120
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
5)
THIS IS A TYPICAL INSTALLATION DRAWING
.
LOCAL CODES AND AUTHORITIES SHOULD BE CONSULTED
.
CONVENIENT FLOOR DRAIN
.
RELIEF VALVE SHOULD BE PIPED VERTICALLY TO A HEIGHT
18
'' ABOVE FLOOR
.
FITTINGS TO PREVENT INTERFERENCE WITH REMOVAL OF BOILER PANELS AND COVERS
.
ALL PIPING AND
ELECTRIC CONNECTIONS
(SERVICE SWITCHES
, CONDUIT BOXES
) SHOULD LIKEWISE BE
6"
AWAY FROM SIDE PANELS
.
1)
FOR ACTUAL SIZES AND LOCATIONS OF PIPING AND OTHER CONNECTIONS TO THE BOILER
, SEE DIMENSIONAL DRAWING
(AP
-A
-739
).
3)
ALL
(*)
ITEMS ARE INCLUDED SEPARATELY IN SHIPMENT FROM FACTORY
.
NOTES
:
2)
SHELL DRAIN VALVE AND CONDENSATE DRAIN TRAP SHOULD BE ARRANGED TO PERMIT THE FLUIDS TO DRAIN FREELY
, BY GRAVITY
, TO A
4)
LOCATE WATER INLET AND OUTLET FITTINGS
(i.
e.
UNIONS
, ELBOWS
, ETC
.)
A MINIMUM OF
6''
FROM BOILER
NORTHVALE
, NJ
07647
INTERNATIONAL
, INC
.
APPD
.
DWN
.BY
SCALE
DATE
DATE
JK
NTS
102307
AERCO
SD
-A
-739
TEMPERATURE GAUGE
P&
T
PRESSURE
&
BALANCING VALVE
ISOLATION VALVE UNION
Y STRAINER
LEGEND
BENCHMARK
1.
5
MIL
. BTU LOW NOx
GAS FIRED BOILER
3-
UNIT INSTALLATION
(2
ZERO
-SIDE
&
1
SEPARATE
)
* CONDENSATE
DRAIN TRAP
1-
1/
2"
NPT
DRAIN CONN
.
BACKFLOW PREVENTER
DIAPHRAGM TYPE EXPANSION TANK
LINE SIZE
BYPASS
SUPPLY
WATER
HEATING SYSTEM SUPPLY
PRESSURE REDUCING FILL VALVE
P&
T
SYSTEM PUMP
CHECK VALVE (TYP
.)
AUTOMATIC AIR VENT
AIR SEPARATOR
GAS SUPPLY
HEATING SYSTEM RETURN
* 1
-1
/2
" MANUAL
SHUTOFF VALVE
P&
T
RELIEF VALVE
(TYP
.)
REV
C
DOWNSTREAM OF THE
2"
MANUAL SHUTOFF VALVE TO BRING THE GAS PRESSURE DOWN TO
2.
0
PSIG
.
6)
WHEN AVAILABLE GAS PRESSURE IS GREATER THAN
2.
0
PSIG
, A LOCK
-UP STYLE REGULATOR MUST BE INSTALLED
7)
A GAS REGULATOR IS MANDATORY FOR THE STATE OF MASSACHUSETTS
, REGARDLESS OF SUPPLY PRESSURE
.
SEE DIAGRAM
1
AT MAXIMUM BTU
/HR INPUT
,
MAINTAIN MINIMUM GAS PRESSURE AT 4.
0"
W
.C
.(FM GAS TRAIN
);
4.
2"
W
.C
. (
IRI
).
MAX
. GAS PRESSURE
=
2.
0
PSIG
. (
SEE NOTE
6)
DRIP TRAP
* 1
-1
/2
" MANUAL
SHUTOFF VALVE
MAINTAIN A REGULATED 4.
0"
W
.C
. (
FM
),
4.
2
W
.C
. (
IRI
)
GAS PRESSURE AT MAX BTU
/HR INPUT
GAS SUPPLY
(TO BOILER
)
(SEE NOTE
7)
Diagram
1
P&
T
DRIP TRAP