5 safety device testing, 6 burner assembly inspection, Benchmark 1.5ln low nox boiler – AERCO BMK 1.5 LN July 2011 User Manual
Page 77: Gf-120
CHAPTER 7: MAINTENANCE
PR2: 05/09/12 Page
77 of 152
Benchmark 1.5LN Low NOx Boiler
Operation and Maintenance Manual
OMM-0041_0D
GF-120
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
Figure 7-4: RSI Manometer Installation Location
7.5 SAFETY DEVICE TESTING
Systematic and thorough tests of the operating and safety devices should be performed to
ensure that they are operating as designed. Certain code requirements, such as ASME CSD-1,
require that these tests be performed on a scheduled basis. Test schedules must conform to
local jurisdictions. The results of the tests should be recorded in a log book. See Chapter 6-
Safety Device Testing Procedures.
7.6 BURNER ASSEMBLY INSPECTION
The burner assembly (part no. 24012) is located at the top of the unit's heat exchanger. The
burner assembly may be hot. Therefore, allow the unit to cool sufficiently before removing the
burner assembly. It should be noted that the complete burner assembly also includes the blower
and air/fuel valve assemblies for the unit.
The following parts will be required for reassembly after burner inspection:
Part No.
Description
81063 Burner Gaskets (Qty=2)
81048 Flame Detector Gasket
81064 Blower Gasket
To inspect or replace the burner assembly:
1. Set the
ON/OFF switch on the control panel, to the OFF position. Disconnect AC power from
the unit and turn off the gas supply.