CHAPTER 7: MAINTENANCE

Page

72 of 152 PR2: 05/09/12

Benchmark 1.5LN Low NOx Boiler

Operation and Maintenance Manual

OMM-0041_0D

GF-120

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288

7.2 IGNITER-INJECTOR

The igniter-injector (part no. 58023) is located on the burner plate at the top of the boiler. In

addition to providing the ignition spark required to light the burner, the igniter-injector also

contains a gas injector tube which connects to the staged ignition assembly. Figure 7-1 shows

the complete burner assembly removed from the boiler and indicates the location of the igniter-

injector flame detector and other related components.
The igniter-injector may be hot, therefore, care should be exercised to avoid burns. It is easier to

remove the igniter-injector from the unit after the unit has cooled to room temperature.

AIR/FUEL

VALVE

STAGED

IGNITION

ASSEMBLY

FLAME

DETECTOR

IGNITOR-

INJECTOR

BLOWER

BURNER

PLATE

BURNER

Figure 7-1: Benchmark 1.5LN Burner Assembly (Shown Removed from Boiler)

To inspect/replace the Igniter:
1. Set the

ON/OFF switch on the control panel, to the OFF position. Disconnect AC power

from the unit

2. Remove the side and top panels from the unit.
3. Disconnect the cable from the igniter-injector (Figure 7-1).
4. Refer to the partial exploded view in Figure 7-2. Using a 7/16” open-end wrench, disconnect

the compression nut securing the gas injector tube of the igniter-injector to the elbow of the

staged ignition assembly. Disconnect the staged ignition assembly from the igniter-injector.