CHAPTER 4: INITIAL START-UP

Page

50 of 152 PR2: 05/09/12

Benchmark 1.5LN Low NOx Boiler

Operation and Maintenance Manual

OMM-0041_0D

GF-120

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288

29. Press the down ▼ arrow key until CAL Voltage 60% is displayed.
30. Press the CHANGE key. CAL Voltage 60% will begin to flash.
31. The oxygen level at the 60% valve position should be as shown below. Also, ensure that

the carbon monoxide (CO) and nitrogen oxide (NOx) readings do not exceed the values

shown.

Table 4-3: Combustion Oxygen Levels for a 60% Air/Fuel Valve Position

Oxygen

%

± 0.2

Carbon

Monoxide

NOx

6.3 %

<50 ppm

<30 ppm

32. If the oxygen level is not within the specified range, adjust the level using the ▲ and ▼

arrow keys. This will adjust the output voltage to the blower motor as indicated on the

display. Pressing the ▲ arrow key increases the oxygen level and pressing the ▼ arrow

key decreases the oxygen level.

33. Once the oxygen level is within the specified range at 60%, press the ENTER key to

store the selected blower output voltage for the 60% valve position.

34. Press the ▲ arrow key until SET Valve Position appears on the C-MORE display.
35. Press the CHANGE key. SET Valve Position will begin to flash.
36. Press the ▼ arrow key until the SET Valve Position reads 45%, then press the ENTER

key.

37. Press the ▼ arrow key until CAL Voltage 45% is displayed.
38. Press the CHANGE key. CAL Voltage 45% will begin to flash.
39. The oxygen level at the 45% valve position should be as shown below. Also, ensure that

the carbon monoxide (CO) and nitrogen oxide (NOx) readings do not exceed the values

shown.

Table 4-4: Combustion Oxygen Levels for a 45% Air/Fuel Valve Position

Oxyge

n %

± 0.2

Carbo

n

Monox

ide

NOx

7.0 %

<50 ppm

<30 ppm

40. If the oxygen level is not within the specified range, adjust the level using the ▲ and ▼

arrow keys. This will adjust the output voltage to the blower motor as indicated on the

display. Pressing the ▲ arrow key increases the oxygen level and pressing the ▼ arrow

key decreases the oxygen level.

41. Once the oxygen level is within the specified range at 45%, press the ENTER key to

store the selected blower output voltage for the 45% valve position.

42. Press the ▲ arrow key until SET Valve Position appears on the C-MORE display.
43. Press the CHANGE key. SET Valve Position will begin to flash.
44. Press the ▼ arrow key until the SET Valve Position reads 30%, then press the ENTER

key.