beautypg.com

1 combustion air from outside the building, 2 combustion air from inside the building, 3 sealed combustion – AERCO BMK 1.5 LN July 2011 User Manual

Page 27: 14 benchmark pump relay option, Benchmark 1.5ln low nox boiler, Gf-120

background image

CHAPTER 2: INSTALLATION

PR2: 05/09/12 Page

27 of 152

Benchmark 1.5LN Low NOx Boiler

Operation and Maintenance Manual

OMM-0041_0D

GF-120

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288

The AERCO Benchmark 1.5 Boiler is UL listed for 100% sealed combustion. It can also be

installed using room air, provided there is an adequate supply. (See paragraph 2.13.3 for more

information concerning sealed combustion air). If the sealed combustion air option is not being

used, an inlet screen will be attached at the air inlet on the top of the unit
The more common methods of supplying combustion air are outlined below. For more

information concerning combustion air, consult the AERCO Benchmark Venting and

Combustion Air Guide, GF-2050.

Combustion Air From Outside the Building

2.13.1

Air supplied from outside the building must be provided through two permanent openings. Each

opening must have a free area of not less than one square inch for each 4000 BTU/H boiler

input. The free area must take into account restrictions such as louvers and bird screens. For

Canada installations, refer to the requirements specified in CSA B149.1-10, 8.4.1 and 8.4.3.

Combustion Air From Inside The Building

2.13.2

When combustion air is provided from within the building, it must be supplied through two

permanent openings in an interior wall. Each opening must have a free area of not less than

one square inch per 1000 BTU/H of total boiler input. The free area must take into account any

restrictions such as louvers.

Sealed Combustion

2.13.3

The AERCO Benchmark 1.5 Boiler is UL listed for 100%-sealed combustion. For sealed

combustion installations, the screen on the air inlet duct of the unit must be removed. The inlet

air ductwork must then be attached directly to the unit’s air inlet.
In a sealed combustion air application, the combustion air ducting pressure losses must be

taken into account when calculating the total maximum allowable venting run. See the AERCO

Benchmark Venting and Combustion Air Guide, GF-2050. When using the boiler in a sealed

combustion air configuration, each unit must have a minimum 6 inch diameter connection at the

unit.

Temporary Combustion Air Filtering During Construction

2.13.4

When the Benchmark 1.5 Boiler is used to provide heat temporarily during ongoing building

construction, accumulated drywall dust, sawdust and similar particles can accumulate in the

unit’s combustion air intake filter and block combustion air flow. In these situations, AERCO

recommends that a disposable air intake filter be installed, temporarily, above the boiler

combustion air inlet.

AERCO recommends that the temporary air filter be cut from a McMaster-Carr part no.

2122K315 Polyester Air Filter Roll Tackfield, ½” thick, 16” wide, or equivalent. Cover the

Benchmark 1.5 air inlet with the blue side of the filter material facing outward to hold the dust on

the outside surface. Maximize the surface area of the filter covering the 8" diameter opening by

creating a dome out of the filter material.
Cover the flared duct opening with the blue side facing outward. During construction check the

filter for dust accumulation and replace it when the accumulation becomes noticeable.

2.14 BENCHMARK PUMP RELAY OPTION

An optional Benchmark pump relay allows the user to turn a pump on/off and open/close a motorized

valve as the boiler cycles on and off on demand. The Pump Delay Timer feature allows the user to keep

the pump running and keep the motorized valve open for up to 30 minutes after the boiler has shut down

and the demand is satisfied.

The Benchmark pump relay (SPDT) contact is rated for: