2 remote setpoint startup, 5 direct drive modes, 1 direct drive field wiring – AERCO BMK 1.5 LN July 2011 User Manual
Page 56: Benchmark 1.5ln low nox boiler, Gf-120
CHAPTER 5: MODE OF OPERATION
Page
56 of 152 PR2: 05/09/12
Benchmark 1.5LN Low NOx Boiler
Operation and Maintenance Manual
OMM-0041_0D
GF-120
AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288
multiple units, each unit’s wiring must conform to the above.
Remote Setpoint Startup
5.4.2
Since this mode of operation is factory preset and the setpoint is being externally controlled, no
startup instructions are necessary. In this mode, the
REMOTE LED will light when the external
signal is present.
To operate the unit in the Manual mode, press the
AUTO/MAN switch. The REMOTE LED will
go off and the
MANUAL LED will light.
To change back to the Remote Setpoint mode, simply press the
AUTO/MAN switch. The
REMOTE LED will again light and the MANUAL LED will go off.
5.5 DIRECT DRIVE MODES
The unit’s air/fuel valve position (% open) can be changed by a remote signal which is typically
sent from an Energy Management System (EMS) or from a Building Automation System (BAS).
The Direct Drive mode can be driven by a current or voltage signal within the following ranges:
•
4-20 mA/1-5 Vdc
•
0-20 mA/0-5 Vdc
The factory default setting for the Direct Drive mode is 4-20 mA/1-5 Vdc. With this setting, a 4
to 20 mA signal, sent by an EMS or BAS is used to change the unit’s valve position from 0% to
100%. A 4 mA/1V signal is equal to a 0% valve position, while a 20 mA /5V signal is equal to a
100% valve position. When a 0-20 mA/0-5 Vdc signal is used, zero is equal to a 0% valve
position.
In addition to the current and voltage signals described above, the Direct Drive mode can also
driven by a RS485 Modbus Network signal from an EMS or BAS.
When in a Direct Drive mode, the unit is a slave to the EMS or BAS and does not have a role in
temperature control. Direct Drive can be used to drive single, or multiple units.
NOTE
If a voltage, rather than current signal is used to control the
remote setpoint, a DIP switch adjustment must be made on the
CPU Board located in the Control Box Assembly. Contact your
local AERCO representative for details.
To enable the Direct Drive Mode, the following menu setting must be made in the Configuration
Menu:
MENU OPTION
SETTING
Boiler Mode
Direct Drive
Remote Signal
4-20mA/1-5V,
0-20mA/0-5V, or
Network
Refer to paragraph 3.3 for instructions on changing menu options.
If the Network setting is selected for RS485 Modbus operation, a valid Comm Address must be
entered in the Setup Menu. Refer to Modbus Communication Manual GF-114 for additional
information.
Direct Drive Field Wiring
5.5.1
The only wiring connections necessary for Direct Drive mode are connection of the remote