CHAPTER 6: SAFETY DEVICE TESTING

Page

64 of 152 PR2: 05/09/12

Benchmark 1.5LN Low NOx Boiler

Operation and Maintenance Manual

OMM-0041_0D

GF-120

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288

5. The unit should start once the adjustable temperature limit switch setting is above the actual

outlet water temperature.

FRONT VIEW

ADJUSTABLE

TEMPERATURE

LIMIT SWITCH

RESET BUTTON

FOR MANUAL

TEMPERATURE

LIMIT SWITCH

SEE

DETAIL “A”

DETAIL “A”

Figure 6-2: Temperature Limit Switch Setting

6. Once the adjustable over-temperature switch setting is approximately at, or just below, the

actual outlet water temperature, the unit should shut down. The

FAULT indicator should

start flashing and a HIGH WATER TEMP SWITCH OPEN fault message should be

displayed. It should not be possible to restart the unit.

7. Reset the adjustable over-temperature switch to its original setting.
8. The unit should start once the adjustable temperature limit switch setting is above the actual

outlet water temperature.