CHAPTER 4: INITIAL START-UP

Page

52 of 152 PR2: 05/09/12

Benchmark 1.5LN Low NOx Boiler

Operation and Maintenance Manual

OMM-0041_0D

GF-120

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913 • Ph: 800-526-0288

2. Disconnect AC power from the unit.
3. Shut off the gas supply to the unit.
4. Remove the manometer and barbed fittings and reinstall the NPT plug using a suitable

pipe thread compound.

5. Remove the combustion analyzer probe from the vent hole. Replace the NPT plug in

the vent hole using a suitable pipe joint compound.

6. Replace the unit’s side panels and front door.

4.6 OVER-TEMPERATURE LIMIT SWITCHES

The unit contains both automatic and manual reset over-temperature limit switches. These

switches are mounted on a plate as shown in Figure 4-6. The switches can be accessed by

opening the front panel door of the unit. The manual reset switch is not adjustable and is

permanently fixed at 200°F. This switch will shut down and lock out the boiler if the water

temperature exceeds 200°F. Following an over-temperature condition, it must be manually reset

by pressing the RESET button before the boiler can be restarted. The automatic reset over-

temperature switch is adjustable and allows the boiler to restart, once the temperature drops

below its temperature setting. Set the automatic over-temperature switch to the desired setting.

FRONT VIEW

ADJUSTABLE

TEMPERATURE

LIMIT SWITCH

RESET BUTTON

FOR MANUAL

TEMPERATURE

LIMIT SWITCH

SEE

DETAIL “A”

DETAIL “A”

Figure 4-6 Over-Temperature Limit Switch Locations