GF-129
Equipment
Point Name
Name
Read
Only
BACnet
Type:ID
N2 Type
N2 ID
Lon SNVT
NAME
Lon SNVT
Lon Direction
ModBus/Unit
Address
06-Display Code
dispcode_228
AV:305
data float
166
nvoDispCode2
28
inc count (9)
Output (non-polled)
30011/228
07-Num Boilers Fired
blrfired_228
AV:306
data float
167
nvoBlrsFired22
8
inc count (9)
Output (non-polled)
30008/228
08-Num Boilers Online
blronline_228
AV:307
data float
168
nvoBlrsOnline2
28
inc count (9)
Output (non-polled)
30009/228
09-Last Blr Fired
blrlast_228
AV:308
data float
169
nvoLastBlrFired
228
inc count (9)
Output (non-polled)
30017/228
18-Net Blr 1 Status
blr9stat_228
AV:309
data float
170
nvoNetBlr1Stat
228
inc count (9)
Output (non-polled)
30026/228
19-Net Blr 2 Status
blr10stat_228
AV:310
data float
178
nvoNetBlr2Stat
228
inc count (9)
Output (non-polled)
30027/228
20-Net Blr 3 Status
blr11stat_228
AV:311
data float
179
nvoNetBlr3Stat
228
inc count (9)
Output (non-polled)
30028/228
21-Net Blr 4 Status
blr12stat_228
AV:312
data float
180
nvoNetBlr4Stat
228
inc count (9)
Output (non-polled)
30029/228