Aerco/protonode gateway, Gf-129, User manual – AERCO ProtoNode Gateway Rev 1 (with internal LEDs) User Manual
Page 59
Page 59 of 64
USER MANUAL
AERCO/ProtoNode Gateway
OMM-0080_0D
AERCO International, Inc.
• 100 Oritani Dr. • Blauvelt, New York 10913 • Phone: 800-526-0288
VD2:011712
1
GF-129
Equipment
Point Name
Name
Read
Only
BACnet
Type:ID
N2 Type
N2 ID
Lon SNVT
NAME
Lon SNVT
Lon Direction
ModBus/Unit
Address
06-Over Temp Alarm
unitstat_22
AV:226
data float
226
nvoEcsStat22
inc count (9)
Output (non-polled)
30075/22
07-Flow Rate
flowrate_22
AV:227
data float
227
nvoEcsFlow22
inc count (9)
Output (non-polled)
30291/22
BMS Addr 128 – for C-More Controller Interface
01-Fire Rate Out
boilerstate_128
AV:260
data float
228
nvoBlrState128
inc count (9)
Output (non-polled)
30005/128
02-Header Set Temp
effectsetpt_128
AV:261
data float
229
nvoEffSetpt128
inc count (9)
Output (non-polled)
30006/128
03-Net Header Set
Temp
setpt_128
AV:262
data float
230
nviSetpt128
inc count (9)
Input (non-polling)
40005/128
04-Header Temp
localsuptemp_1
28
AV:263
data float
231
nvoLocSupTmp
128
inc count (9)
Output (non-polled)
30002/128
05-Outside Air Temp
localoatemp_12
8
AV:264
data float
232
nvoLocOATmp
128
inc count (9)
Output (non-polled)
30003/128
06-Display Code
dispcode_128
AV:265
data float
233
nvoDispCode1
28
inc count (9)
Output (non-polled)
30011/128
07-Num Boilers Fired
blrfired_128
AV:266
data float
234
nvoBlrsFired12
8
inc count (9)
Output (non-polled)
30008/128
08-Num Boilers Online
blronline_128
AV:267
data float
235
nvoBlrsOnline1
28
inc count (9)
Output (non-polled)
30009/128
09-Last Blr Fired
blrlast_128
AV:268
data float
236
nvoLastBlrFired
128
inc count (9)
Output (non-polled)
30017/128
10-Boiler 1 Status
blr1stat_128
AV:269
data float
237
nvoBlr1Stat128
inc count (9)
Output (non-polled)
30018/128
11-Boiler 2 Status
blr2stat_128
AV:270
data float
238
nvoBlr2Stat128
inc count (9)
Output (non-polled)
30019/128
12-Boiler 3 Status
blr3stat_128
AV:271
data float
239
nvoBlr3Stat128
inc count (9)
Output (non-polled)
30020/128
13-Boiler 4 Status
blr4stat_128
AV:272
data float
240
nvoBlr4Stat128
inc count (9)
Output (non-polled)
30021/128
14-Boiler 5 Status
blr5stat_128
AV:273
data float
241
nvoBlr5Stat128
inc count (9)
Output (non-polled)
30022/128
15-Boiler 6 Status
blr6stat_128
AV:274
data float
242
nvoBlr6Stat128
inc count (9)
Output (non-polled)
30023/128
16-Boiler 7 Status
blr7stat_128
AV:275
data float
243
nvoBlr7Stat128
inc count (9)
Output (non-polled)
30024/128
C.2.6 - Twelve C-Mores, Six ECS/SP, Four Modulex, and Two ACS/BMS II (Cont.)