beautypg.com

Aerco/protonode gateway, Gf-129 – AERCO ProtoNode Gateway Rev 1 (with internal LEDs) User Manual

Page 21

background image

Page 21 of 64

USER MANUAL

AERCO/ProtoNode Gateway

OMM-0080_0D

AERCO International, Inc.

• 100 Oritani Dr. • Blauvelt, New York 10913 • Phone: 800-526-0288

VD2:011712
1

GF-129



Figure 15. AERCO/ProtoNode Gateway LER ProtoCessor Board Indication LED Locations

LED

DESCRIPTION

Power

This is the power light and should show steady green at all times when the ProtoNode LER is
powered.

System

Error

The SYS ERR LED will flash once on power up and flash once 15 seconds after power up. A
steady red light will indicate there is a system error on the ProtoNode LER. If this occurs,
immediately report the related “system error” shown in the error screen of the RUI interface
to AERCO International for evaluation.

Comm.

Error

The COMM ERR LED will flash once on power up and flash once 15 seconds after power up. A
steady red light will indicate a communication error has occurred. To establish the cause of
the error, go to the error screen of the RUI interface.

Config.

Error

The Config ERR LED will flash once on power up and flash once 15 seconds after power up. A
steady amber light will indicate a configuration error exists in the active configuration. See the
Error Screen in the Remote User Interface for a description of the configuration error.

Node

Offline

The Node Offline LED will flash once on power up and flash once 15 seconds after power up. If
the Node Offline LED stays on solid, a Node Offline condition has occurred.

RUN

(PIO)

The RUN LED will start flashing 20 seconds after power indicating normal operation. The
ProtoNode LER will be able to access RUINET once this LED starts flashing.

PIC Run

The PIC RUN LED will flash indicating normal operation.

PIC

Error

The PIC ERR LED will go on solid indicating there is a PIC error.

LON-TX

On normal operation of ProtoNode LER, the TX LED will flash when a message is sent on the
Lon port of the ProtoNode.

LON-RX

On normal operation of ProtoNode LER, the RX LED will flash when a message is received on
the Lon port of the ProtoNode.

LON-

SRV

The LON-SRV LED will flash if the ProtoNode is configured for implicit addressing and not
commissioned. LED will be off if the ProtoNode is configured for implicit addressing and
commissioned or if it is configured for explicit addressing.

LON TX

LON RX

LON-SRV

Comm. Error

Run (PIO)

Config. Error

System Error

Node Offline

PIC Error
Unused
Unused

PIC Run

Power