Aerco/protonode gateway, Gf-129, User manual – AERCO ProtoNode Gateway Rev 1 (with internal LEDs) User Manual
Page 44
Page 44 of 64
USER MANUAL
AERCO/ProtoNode Gateway
OMM-0080_0D
AERCO International, Inc.
• 100 Oritani Dr. • Blauvelt, New York 10913 • Phone: 800-526-0288
VD2:011712
1
GF-129
Equipment
Point Name
Name
Read
Only
BACnet Type:ID
N2 Type
N2 ID
Lon SNVT NAME
Lon SNVT
Lon Direction
ModBus/Unit
Address
BMS Addr 128
01-Fire Rate Out
boilerstate_13
AV:31
data float
121
nvoBlrState
inc count (9)
Output (non-polled)
30005/128
02-Header Set Temp
effectsetpt_13
AV:32
data float
122
nvoEffSetpt
inc count (9)
Output (non-polled)
30006/128
03-Net Header Set
Temp
setpt_13
AV:33
data float
123
nviSetpt
inc count (9)
Input (non-polling)
40005/128
04-Header Temp
localsuptemp_13
AV:34
data float
124
nvoLocSupTmp
inc count (9)
Output (non-polled)
30002/128
05-Outside Air Temp
localoatemp_13
AV:35
data float
125
nvoLocOATmp
inc count (9)
Output (non-polled)
30003/128
06-Display Code
dispcode_13
AV:36
data float
126
nvoDispCode
inc count (9)
Output (non-polled)
30011/128
07-Num Boilers Fired
blrfired_13
AV:37
data float
127
nvoBlrsFired
inc count (9)
Output (non-polled)
30008/128
08-Num Boilers
Online
blronline_13
AV:38
data float
128
nvoBlrsOnline
inc count (9)
Output (non-polled)
30009/128
09-Last Blr Fired
blrlast_13
AV:39
data float
129
nvoLastBlrFired
inc count (9)
Output (non-polled)
30017/128
10-Boiler 1 Status
blr1stat_13
AV:40
data float
130
nvoBlr1Stat
inc count (9)
Output (non-polled)
30018/128
11-Boiler 2 Status
blr2stat_13
AV:41
data float
131
nvoBlr2Stat
inc count (9)
Output (non-polled)
30019/128
12-Boiler 3 Status
blr3stat_13
AV:48
data float
132
nvoBlr3Stat
inc count (9)
Output (non-polled)
30020/128
13-Boiler 4 Status
blr4stat_13
AV:1
data float
133
nvoBlr4Stat
inc count (9)
Output (non-polled)
30021/128
14-Boiler 5 Status
blr5stat_13
AV:2
data float
134
nvoBlr5Stat
inc count (9)
Output (non-polled)
30022/128
15-Boiler 6 Status
blr6stat_13
AV:3
data float
135
nvoBlr6Stat
inc count (9)
Output (non-polled)
30023/128
16-Boiler 7 Status
blr7stat_13
AV:4
data float
136
nvoBlr7Stat
inc count (9)
Output (non-polled)
30024/128
17-Boiler 8 Status
blr8stat_13
AV:5
data float
137
nvoBlr8Stat
inc count (9)
Output (non-polled)
30025/128
18-Net Blr 1 Status
blr9stat_13
AV:6
data float
138
nvoNetBlr1Stat
inc count (9)
Output (non-polled)
30026/128
19-Net Blr 2 Status
blr10stat_13
AV:7
data float
139
nvoNetBlr2Stat
inc count (9)
Output (non-polled)
30027/128
20-Net Blr 3 Status
blr11stat_13
AV:8
data float
140
nvoNetBlr3Stat
inc count (9)
Output (non-polled)
30028/128
21-Net Blr 4 Status
blr12stat_13
AV:9
data float
141
nvoNetBlr4Stat
inc count (9)
Output (non-polled)
30029/128
22-Net Blr 5 Status
blr13stat_13
AV:10
data float
142
nvoNetBlr5Stat
inc count (9)
Output (non-polled)
30030/128
23-Net Blr 6 Status
blr14stat_13
AV:11
data float
143
nvoNetBlr6Stat
inc count (9)
Output (non-polled)
30031/128
24-Net Blr 7 Status
blr15stat_13
AV:12
data float
144
nvoNetBlr7Stat
inc count (9)
Output (non-polled)
30032/128
25-Net Blr 8 Status
blr16stat_13
AV:13
data float
145
nvoNetBlr8Stat
inc count (9)
Output (non-polled)
30033/128
26-Net Blr 9 Status
blr17stat_13
AV:14
data float
146
nvoNetBlr9Stat
inc count (9)
Output (non-polled)
30034/128
27-Net Blr 10 Status
blr18stat_13
AV:15
data float
147
nvoNetBlr10Stat
inc count (9)
Output (non-polled)
30035/128
28-Net Blr 11 Status
blr19stat_13
AV:16
data float
148
nvoNetBlr11Stat
inc count (9)
Output (non-polled)
30036/128
29-Net Blr 12 Status
blr20stat_13
AV:17
data float
149
nvoNetBlr12Stat
inc count (9)
Output (non-polled)
30037/128
C.2.3 - Twelve C-Mores and One ACS/BMS II/BMS (Cont.)