Aerco/protonode gateway, Gf-129, User manual – AERCO ProtoNode Gateway Rev 1 (with internal LEDs) User Manual
Page 37
Page 37 of 64
USER MANUAL
AERCO/ProtoNode Gateway
OMM-0080_0D
AERCO International, Inc.
• 100 Oritani Dr. • Blauvelt, New York 10913 • Phone: 800-526-0288
VD2:011712
1
GF-129
Equipment
Point Name
Name
Read
Only
BACnet Type:ID
N2 Type
N2 ID
Lon SNVT NAME
Lon SNVT
Lon Direction
ModBus/Unit
Address
10-Run Hours
runhours_2
AV:45
data float
20
nvoRunHours2
51
Output (non-polled)
30014-30015/2
Blr Addr 3
01-Fire Rate Out
boilerstate_3
AV:54
data float
21
nvoBlrState3
inc count (9)
Output (non-polled)
30009/3
02-Active Setpoint
effectsetpt_3
AV:55
data float
22
nvoEffSetpt3
inc count (9)
Output (non-polled)
30017/3
03-Net Remote Setpt
setpt_3
AV:56
data float
23
nviSetpt3
inc count (9)
Input (non-polling)
40001/3
05-Fire Rate In
boilerload_3
AV:60
data float
25
nvoBlrLoad3
inc count (9)
Output (non-polled)
30018/3
06-Outlet Temp
localsuptemp_3
AV:61
data float
26
nvoLocSupTmp3
inc count (9)
Output (non-polled)
30003/3
07-Display Code
dispcode_3
AV:62
data float
27
nvoDispCode3
inc count (9)
Output (non-polled)
30001/3
08-Unit Status
unitstat_3
AV:63
data float
28
nvoUnitStat3
inc count (9)
Output (non-polled)
30002/3
09-Run Cycles
runcycles_3
AV:58
data float
29
nvoRunCycles3
51
Output (non-polled)
30012-30013/3
10-Run Hours
runhours_3
AV:59
data float
30
nvoRunHours3
51
Output (non-polled)
30014-30015/3
Blr Addr 4
01-Fire Rate Out
boilerstate_4
AV:70
data float
31
nvoBlrState4
inc count (9)
Output (non-polled)
30009/4
02-Active Setpoint
effectsetpt_4
AV:71
data float
32
nvoEffSetpt4
inc count (9)
Output (non-polled)
30017/4
03-Net Remote Setpt
setpt_4
AV:72
data float
33
nviSetpt4
inc count (9)
Input (non-polling)
40001/4
05-Fire Rate In
boilerload_4
AV:73
data float
35
nvoBlrLoad4
inc count (9)
Output (non-polled)
30018/4
06-Outlet Temp
localsuptemp_4
AV:65
data float
36
nvoLocSupTmp4
inc count (9)
Output (non-polled)
30003/4
07-Display Code
dispcode_4
AV:66
data float
37
nvoDispCode4
inc count (9)
Output (non-polled)
30001/4
08-Unit Status
unitstat_4
AV:67
data float
38
nvoUnitStat4
inc count (9)
Output (non-polled)
30002/4
09-Run Cycles
runcycles_4
AV:68
data float
39
nvoRunCycles4
51
Output (non-polled)
30012-30013/4
10-Run Hours
runhours_4
AV:69
data float
40
nvoRunHours4
51
Output (non-polled)
30014-30015/4
Blr Addr 5
01-Fire Rate Out
boilerstate_5
AV:80
data float
41
nvoBlrState5
inc count (9)
Output (non-polled)
30009/5
02-Active Setpoint
effectsetpt_5
AV:81
data float
42
nvoEffSetpt5
inc count (9)
Output (non-polled)
30017/5
03-Net Remote Setpt
setpt_5
AV:82
data float
43
nviSetpt5
inc count (9)
Input (non-polling)
40001/5
05-Fire Rate In
boilerload_5
AV:74
data float
45
nvoBlrLoad5
inc count (9)
Output (non-polled)
30018/5
06-Outlet Temp
localsuptemp_5
AV:75
data float
46
nvoLocSupTmp5
inc count (9)
Output (non-polled)
30003/5
07-Display Code
dispcode_5
AV:76
data float
47
nvoDispCode5
inc count (9)
Output (non-polled)
30001/5
08-Unit Status
unitstat_5
AV:77
data float
48
nvoUnitStat5
inc count (9)
Output (non-polled)
30002/5
09-Run Cycles
runcycles_5
AV:78
data float
49
nvoRunCycles5
51
Output (non-polled)
30012-30013/5
10-Run Hours
runhours_5
AV:79
data float
50
nvoRunHours5
51
Output (non-polled)
30014-30015/5
Blr Addr 6
01-Fire Rate Out
boilerstate_6
AV:90
data float
51
nvoBlrState6
inc count (9)
Output (non-polled)
30009/6
C.2.2 - Eight C-Mores and One ACS/BMS II/BMS (Cont.)