C.2.5 – ecs …………………………………………………………………………………...….47, Aerco/protonode gateway, Gf-129 – AERCO ProtoNode Gateway Rev 1 (with internal LEDs) User Manual
Page 47: User manual
![background image](/manuals/659313/47/background.png)
Page 47 of 64
USER MANUAL
AERCO/ProtoNode Gateway
OMM-0080_0D
AERCO International, Inc.
• 100 Oritani Dr. • Blauvelt, New York 10913 • Phone: 800-526-0288
VD2:011712
1
GF-129
C.2.5 – ECS/SP
Equipment
Point Name
Name
Read
Only
BACnet
Type:ID
N2 Type
N2
ID
Lon SNVT NAME
Lon SNVT
Lon Direction
ModBus/Unit Address
E Valve Addr 29
01-Cntl Output
Signal
boilerstate_1
AV:11
data float
1
nvoEcsState29
inc count
(9)
Output (non-polled)
30004/29
02-Setpoint
effectsetpt_1
AV:80
data float
2
nvoEcsSetpt29
inc count
(9)
Output (non-polled)
30006/29
03-RmSetpt
rmsetpt_1
AV:81
data float
3
nviEcsSetptRq29
inc count
(9)
Input (non-polling)
40027/29
04-Outlet Temp
localsuptemp_1
AV:84
data float
4
nvoEcsSupTmp29
inc count
(9)
Output (non-polled)
30002/29
05-FBk Sensor
Temp
localrettemp_1
AV:1
data float
5
nvoEcsRetTmp29
inc count
(9)
Output (non-polled)
30290/29
06-Over Temp
Alarm
unitstat_1
AV:86
data float
6
nvoEcsStat29
inc count
(9)
Output (non-polled)
30075/29
07-Flow Rate
flowrate_1
AV:2
data float
7
nvoEcsFlow29
inc count
(9)
Output (non-polled)
30291/29
E Valve Addr 30
01-Cntl Output
Signal
boilerstate_2
AV:12
data float
8
nvoEcsState30
inc count
(9)
Output (non-polled)
30004/30
02-Setpoint
effectsetpt_2
AV:3
data float
9
nvoEcsSetpt30
inc count
(9)
Output (non-polled)
30006/30
03-RmSetpt
rmsetpt_2
AV:4
data float
10
nviEcsSetptRq30
inc count
(9)
Input (non-polling)
40027/30
04-Outlet Temp
localsuptemp_2
AV:5
data float
11
nvoEcsSupTmp30
inc count
(9)
Output (non-polled)
30002/30
05-FBk Sensor
Temp
localrettemp_2
AV:6
data float
12
nvoEcsRetTmp30
inc count
(9)
Output (non-polled)
30290/30
06-Over Temp
Alarm
unitstat_2
AV:7
data float
13
nvoEcsStat30
inc count
(9)
Output (non-polled)
30075/30
07-Flow Rate
flowrate_2
AV:8
data float
14
nvoEcsFlow30
inc count
(9)
Output (non-polled)
30291/30
E Valve Addr 31
01-Cntl Output
Signal
boilerstate_3
AV:9
data float
15
nvoEcsState31
inc count
(9)
Output (non-polled)
30004/31
02-Setpoint
effectsetpt_3
AV:150
data float
16
nvoEcsSetpt31
inc count
(9)
Output (non-polled)
30006/31
03-RmSetpt
rmsetpt_3
AV:151
data float
17
nviEcsSetptRq31
inc count
(9)
Input (non-polling)
40027/31
04-Outlet Temp
localsuptemp_3
AV:152
data float
18
nvoEcsSupTmp31
inc count
(9)
Output (non-polled)
30002/31
05-FBk Sensor
Temp
localrettemp_3
AV:153
data float
19
nvoEcsRetTmp31
inc count
(9)
Output (non-polled)
30290/31
06-Over Temp
Alarm
unitstat_3
AV:154
data float
20
nvoEcsStat31
inc count
(9)
Output (non-polled)
30075/31