1
GF-129
Equipment
Point Name
Name
Read
Only
BACnet Type:ID
N2 Type
N2 ID
Lon SNVT NAME
Lon SNVT
Lon Direction
ModBus/Unit
Address
02-Active Setpoint
effectsetpt_6
AV:91
data float
52
nvoEffSetpt6
inc count (9)
Output (non-polled)
30017/6
03-Net Remote Setpt
setpt_6
AV:92
data float
53
nviSetpt6
inc count (9)
Input (non-polling)
40001/6
05-Fire Rate In
boilerload_6
AV:84
data float
55
nvoBlrLoad6
inc count (9)
Output (non-polled)
30018/6
06-Outlet Temp
localsuptemp_6
AV:85
data float
56
nvoLocSupTmp6
inc count (9)
Output (non-polled)
30003/6
07-Display Code
dispcode_6
AV:86
data float
57
nvoDispCode6
inc count (9)
Output (non-polled)
30001/6
08-Unit Status
unitstat_6
AV:87
data float
58
nvoUnitStat6
inc count (9)
Output (non-polled)
30002/6
09-Run Cycles
runcycles_6
AV:88
data float
59
nvoRunCycles6
51
Output (non-polled)
30012-30013/6
10-Run Hours
runhours_6
AV:89
data float
60
nvoRunHours6
51
Output (non-polled)
30014-30015/6
Blr Addr 7
01-Fire Rate Out
boilerstate_7
AV:100
data float
61
nvoBlrState7
inc count (9)
Output (non-polled)
30009/7
02-Active Setpoint
effectsetpt_7
AV:101
data float
62
nvoEffSetpt7
inc count (9)
Output (non-polled)
30017/7
03-Net Remote Setpt
setpt_7
AV:102
data float
63
nviSetpt7
inc count (9)
Input (non-polling)
40001/7
05-Fire Rate In
boilerload_7
AV:94
data float
65
nvoBlrLoad7
inc count (9)
Output (non-polled)
30018/7
06-Outlet Temp
localsuptemp_7
AV:95
data float
66
nvoLocSupTmp7
inc count (9)
Output (non-polled)
30003/7
07-Display Code
dispcode_7
AV:96
data float
67
nvoDispCode7
inc count (9)
Output (non-polled)
30001/7
08-Unit Status
unitstat_7
AV:97
data float
68
nvoUnitStat7
inc count (9)
Output (non-polled)
30002/7
09-Run Cycles
runcycles_7
AV:98
data float
69
nvoRunCycles7
51
Output (non-polled)
30012-30013/7
10-Run Hours
runhours_7
AV:99
data float
70
nvoRunHours7
51
Output (non-polled)
30014-30015/7
Blr Addr 8
01-Fire Rate Out
boilerstate_8
AV:110
data float
71
nvoBlrState8
inc count (9)
Output (non-polled)
30009/8
02-Active Setpoint
effectsetpt_8
AV:111
data float
72
nvoEffSetpt8
inc count (9)
Output (non-polled)
30017/8
03-Net Remote Setpt
setpt_8
AV:112
data float
73
nviSetpt8
inc count (9)
Input (non-polling)
40001/8
05-Fire Rate In
boilerload_8
AV:104
data float
75
nvoBlrLoad8
inc count (9)
Output (non-polled)
30018/8
06-Outlet Temp
localsuptemp_8
AV:105
data float
76
nvoLocSupTmp8
inc count (9)
Output (non-polled)
30003/8
07-Display Code
dispcode_8
AV:106
data float
77
nvoDispCode8
inc count (9)
Output (non-polled)
30001/8
08-Unit Status
unitstat_8
AV:107
data float
78
nvoUnitStat8
inc count (9)
Output (non-polled)
30002/8
09-Run Cycles
runcycles_8
AV:108
data float
79
nvoRunCycles8
51
Output (non-polled)
30012-30013/8
10-Run Hours
runhours_8
AV:109
data float
80
nvoRunHours8
51
Output (non-polled)
30014-30015/8
BMS Addr 128
01-Fire Rate Out
boilerstate_13
AV:31
data float
121
nvoBlrState
inc count (9)
Output (non-polled)
30005/128
02-Header Set Temp
effectsetpt_13
AV:32
data float
122
nvoEffSetpt
inc count (9)
Output (non-polled)
30006/128
03-Net Header Set
Temp
setpt_13
AV:33
data float
123
nviSetpt
inc count (9)
Input (non-polling)
40005/128
C.2.2 - Eight C-Mores and One ACS/BMS II/BMS (Cont.)