Aerco/protonode gateway, Gf-129, User manual – AERCO ProtoNode Gateway Rev 1 (with internal LEDs) User Manual
Page 46
Page 46 of 64
USER MANUAL
AERCO/ProtoNode Gateway
OMM-0080_0D
AERCO International, Inc.
• 100 Oritani Dr. • Blauvelt, New York 10913 • Phone: 800-526-0288
VD2:011712
1
GF-129
Equipment
Point Name
Name
Read
Only
BACnet
Type:ID
N2 Type
N2 ID
Lon SNVT NAME
Lon SNVT
Lon Direction
ModBus/Unit Address
05-Mod Lev In
boilerload_2
AV:148
data float
157
nvoMlxLoad2
inc count (9)
Output (non-polled)
41201/2
06-Flow Sens Temp
localsuptemp_2
AV:149
data float
158
nvoMlxSupTmp2
inc count (9)
Output (non-polled)
41003/2
07-Display Code
dispcode_2
AV:150
data float
159
nvoMlxDispCode2
inc count (9)
Output (non-polled)
30001/2
11-Error Code
errcode_2
AV:4
data float
160
nvoMlxErrCode2
51
Output (non-polled)
40001/2
08-Unit Status
unitstat_2
AV:151
data float
161
nvoMlxStat2
inc count (9)
Output (non-polled)
30002/2
09-Ret Flow Temp
returntemp_2
AV:5
data float
162
nvoMlxRetTmp2
inc count (9)
Output (non-polled)
41004/2
Mlx Addr 3
01-Act Mod Lev
boilerstate_3
AV:18
data float
164
nvoMlxState3
inc count (9)
Output (non-polled)
41009/3
02-Target Setpoint
effectsetpt_3
AV:19
data float
165
nvoMlxSetpt3
inc count (9)
Output (non-polled)
41019/3
03-Req Outlet Temp
setpt_3
AV:20
data float
166
nviMlxSetptRq3
inc count (9)
Input (non-polling)
41005/3
04-Net Direct Drive
boilercmd_3
AV:21
data float
167
nviMlxCmd3
inc count (9)
Input (non-polling)
40002/3
05-Mod Lev In
boilerload_3
AV:22
data float
168
nvoMlxLoad3
inc count (9)
Output (non-polled)
41201/3
06-Flow Sens Temp
localsuptemp_3
AV:23
data float
169
nvoMlxSupTmp3
inc count (9)
Output (non-polled)
41003/3
07-Display Code
dispcode_3
AV:24
data float
170
nvoMlxDispCode3
inc count (9)
Output (non-polled)
30001/3
11-Error Code
errcode_3
AV:7
data float
171
nvoMlxErrCode3
51
Output (non-polled)
40001/3
08-Unit Status
unitstat_3
AV:25
data float
172
nvoMlxStat3
inc count (9)
Output (non-polled)
30002/3
09-Ret Flow Temp
returntemp_3
AV:8
data float
173
nvoMlxRetTmp3
inc count (9)
Output (non-polled)
41004/3
Mlx Addr 4
01-Act Mod Lev
boilerstate_4
AV:28
data float
175
nvoMlxState4
inc count (9)
Output (non-polled)
41009/4
02-Target Setpoint
effectsetpt_4
AV:29
data float
176
nvoMlxSetpt4
inc count (9)
Output (non-polled)
41019/4
03-Req Outlet Temp
setpt_4
AV:30
data float
177
nviMlxSetptRq4
inc count (9)
Input (non-polling)
41005/4
04-Net Direct Drive
boilercmd_4
AV:42
data float
178
nviMlxCmd4
inc count (9)
Input (non-polling)
40002/4
05-Mod Lev In
boilerload_4
AV:43
data float
179
nvoMlxLoad4
inc count (9)
Output (non-polled)
41201/4
06-Flow Sens Temp
localsuptemp_4
AV:44
data float
180
nvoMlxSupTmp4
inc count (9)
Output (non-polled)
41003/4
07-Display Code
dispcode_4
AV:45
data float
181
nvoMlxDispCode4
inc count (9)
Output (non-polled)
30001/4
11-Error Code
errcode_4
AV:10
data float
182
nvoMlxErrCode4
51
Output (non-polled)
40001/4
08-Unit Status
unitstat_4
AV:46
data float
183
nvoMlxStat4
inc count (9)
Output (non-polled)
30002/4
09-Ret Flow Temp
returntemp_4
AV:11
data float
184
nvoMlxRetTmp4
inc count (9)
Output (non-polled)
41004/4
C.2.4 Modulex and One ACS/BMS II (Cont.)