Aerco/protonode gateway, Gf-129, User manual – AERCO ProtoNode Gateway Rev 1 (with internal LEDs) User Manual
Page 43
![background image](/manuals/659313/43/background.png)
Page 43 of 64
USER MANUAL
AERCO/ProtoNode Gateway
OMM-0080_0D
AERCO International, Inc.
• 100 Oritani Dr. • Blauvelt, New York 10913 • Phone: 800-526-0288
VD2:011712
1
GF-129
Equipment
Point Name
Name
Read
Only
BACnet Type:ID
N2 Type
N2 ID
Lon SNVT NAME
Lon SNVT
Lon Direction
ModBus/Unit
Address
Blr Addr 10
01-Fire Rate Out
boilerstate_10
AV:130
data float
91
nvoBlrState10
inc count (9)
Output (non-polled)
30009/10
02-Active Setpoint
effectsetpt_10
AV:131
data float
92
nvoEffSetpt10
inc count (9)
Output (non-polled)
30017/10
03-Net Remote Setpt
setpt_10
AV:132
data float
93
nviSetpt10
inc count (9)
Input (non-polling)
40001/10
05-Fire Rate In
boilerload_10
AV:124
data float
95
nvoBlrLoad10
inc count (9)
Output (non-polled)
30018/10
06-Outlet Temp
localsuptemp_10
AV:125
data float
96
nvoLocSupTmp10
inc count (9)
Output (non-polled)
30003/10
07-Display Code
dispcode_10
AV:126
data float
97
nvoDispCode10
inc count (9)
Output (non-polled)
30001/10
08-Unit Status
unitstat_10
AV:127
data float
98
nvoUnitStat10
inc count (9)
Output (non-polled)
30002/10
09-Run Cycles
runcycles_10
AV:128
data float
99
nvoRunCycles10
51
Output (non-polled)
30012-30013/10
10-Run Hours
runhours_10
AV:129
data float
100
nvoRunHours10
51
Output (non-polled)
30014-30015/10
Blr Addr 11
01-Fire Rate Out
boilerstate_11
AV:140
data float
101
nvoBlrState11
inc count (9)
Output (non-polled)
30009/11
02-Active Setpoint
effectsetpt_11
AV:141
data float
102
nvoEffSetpt11
inc count (9)
Output (non-polled)
30017/11
03-Net Remote Setpt
setpt_11
AV:142
data float
103
nviSetpt11
inc count (9)
Input (non-polling)
40001/11
05-Fire Rate In
boilerload_11
AV:134
data float
105
nvoBlrLoad11
inc count (9)
Output (non-polled)
30018/11
06-Outlet Temp
localsuptemp_11
AV:135
data float
106
nvoLocSupTmp11
inc count (9)
Output (non-polled)
30003/11
07-Display Code
dispcode_11
AV:136
data float
107
nvoDispCode11
inc count (9)
Output (non-polled)
30001/11
08-Unit Status
unitstat_11
AV:137
data float
108
nvoUnitStat11
inc count (9)
Output (non-polled)
30002/11
09-Run Cycles
runcycles_11
AV:138
data float
109
nvoRunCycles11
51
Output (non-polled)
30012-30013/11
10-Run Hours
runhours_11
AV:139
data float
110
nvoRunHours11
51
Output (non-polled)
30014-30015/11
Blr Addr 12
01-Fire Rate Out
boilerstate_12
AV:150
data float
111
nvoBlrState12
inc count (9)
Output (non-polled)
30009/12
02-Active Setpoint
effectsetpt_12
AV:151
data float
112
nvoEffSetpt12
inc count (9)
Output (non-polled)
30017/12
03-Net Remote Setpt
setpt_12
AV:152
data float
113
nviSetpt12
inc count (9)
Input (non-polling)
40001/12
05-Fire Rate In
boilerload_12
AV:144
data float
115
nvoBlrLoad12
inc count (9)
Output (non-polled)
30018/12
06-Outlet Temp
localsuptemp_12
AV:145
data float
116
nvoLocSupTmp12
inc count (9)
Output (non-polled)
30003/12
07-Display Code
dispcode_12
AV:146
data float
117
nvoDispCode12
inc count (9)
Output (non-polled)
30001/12
08-Unit Status
unitstat_12
AV:147
data float
118
nvoUnitStat12
inc count (9)
Output (non-polled)
30002/12
09-Run Cycles
runcycles_12
AV:148
data float
119
nvoRunCycles12
51
Output (non-polled)
30012-30013/12
10-Run Hours
runhours_12
AV:149
data float
120
nvoRunHours12
51
Output (non-polled)
30014-30015/12
C.2.3 - Twelve C-Mores and One ACS/BMS II/BMS (Cont.)