C.2.2 - eight c-mores and one acs/bms ii/bms, Aerco/protonode gateway, Gf-129 – AERCO ProtoNode Gateway Rev 1 (with internal LEDs) User Manual
Page 36: User manual
![background image](/manuals/659313/36/background.png)
Page 36 of 64
USER MANUAL
AERCO/ProtoNode Gateway
OMM-0080_0D
AERCO International, Inc.
• 100 Oritani Dr. • Blauvelt, New York 10913 • Phone: 800-526-0288
VD2:011712
1
GF-129
Equipment
Point Name
Name
Read Only BACnet Type:ID N2 Type N2 ID Lon SNVT NAME Lon SNVT
Lon Direction
ModBus/Unit Addr.
14-Boiler 5 Status
blr5stat_5
AV:2
data float 54 nvoBlr5Stat
inc count (9) Output (non-polled)
30022/128
15-Boiler 6 Status
blr6stat_5
AV:3
data float 55 nvoBlr6Stat
inc count (9) Output (non-polled)
30023/128
16-Boiler 7 Status
blr7stat_5
AV:4
data float 56 nvoBlr7Stat
inc count (9) Output (non-polled)
30024/128
17-Boiler 8 Status
blr8stat_5
AV:5
data float 57 nvoBlr8Stat
inc count (9) Output (non-polled)
30025/128
18-Net Blr 1 Status
blr9stat_5
AV:6
data float 58 nvoNetBlr1Stat inc count (9) Output (non-polled)
30026/128
19-Net Blr 2 Status
blr10stat_5
AV:7
data float 59 nvoNetBlr2Stat inc count (9) Output (non-polled)
30027/128
20-Net Blr 3 Status
blr11stat_5
AV:8
data float 60 nvoNetBlr3Stat inc count (9) Output (non-polled)
30028/128
21-Net Blr 4 Status
blr12stat_5
AV:9
data float 61 nvoNetBlr4Stat inc count (9) Output (non-polled)
30029/128
C.2.2 - Eight C-Mores and One ACS/BMS II/BMS
Equipment
Point Name
Name
Read
Only
BACnet Type:ID
N2 Type
N2 ID
Lon SNVT NAME
Lon SNVT
Lon Direction
ModBus/Unit
Address
Blr Addr 1
01-Fire Rate Out
boilerstate_1
AV:26
data float
1
nvoBlrState1
inc count (9)
Output (non-polled)
30009/1
02-Active Setpoint
effectsetpt_1
AV:27
data float
2
nvoEffSetpt1
inc count (9)
Output (non-polled)
30017/1
03-Net Remote Setpt
setpt_1
AV:24
data float
3
nviSetpt1
inc count (9)
Input (non-polling)
40001/1
05-Fire Rate In
boilerload_1
AV:28
data float
5
nvoBlrLoad1
inc count (9)
Output (non-polled)
30018/1
06-Outlet Temp
localsuptemp_1
AV:29
data float
6
nvoLocSupTmp1
inc count (9)
Output (non-polled)
30003/1
07-Display Code
dispcode_1
AV:22
data float
7
nvoDispCode1
inc count (9)
Output (non-polled)
30001/1
08-Unit Status
unitstat_1
AV:23
data float
8
nvoUnitStat1
inc count (9)
Output (non-polled)
30002/1
09-Run Cycles
runcycles_1
AV:42
data float
9
nvoRunCycles1
51
Output (non-polled)
30012-30013/1
10-Run Hours
runhours_1
AV:43
data float
10
nvoRunHours1
51
Output (non-polled)
30014-30015/1
Blr Addr 2
01-Fire Rate Out
boilerstate_2
AV:30
data float
11
nvoBlrState2
inc count (9)
Output (non-polled)
30009/2
02-Active Setpoint
effectsetpt_2
AV:46
data float
12
nvoEffSetpt2
inc count (9)
Output (non-polled)
30017/2
03-Net Remote Setpt
setpt_2
AV:47
data float
13
nviSetpt2
inc count (9)
Input (non-polling)
40001/2
05-Fire Rate In
boilerload_2
AV:50
data float
15
nvoBlrLoad2
inc count (9)
Output (non-polled)
30018/2
06-Outlet Temp
localsuptemp_2
AV:51
data float
16
nvoLocSupTmp2
inc count (9)
Output (non-polled)
30003/2
07-Display Code
dispcode_2
AV:52
data float
17
nvoDispCode2
inc count (9)
Output (non-polled)
30001/2
08-Unit Status
unitstat_2
AV:53
data float
18
nvoUnitStat2
inc count (9)
Output (non-polled)
30002/2
09-Run Cycles
runcycles_2
AV:44
data float
19
nvoRunCycles2
51
Output (non-polled)
30012-30013/2
C.2.1 - Four C-Mores and One ACS/BMS II/BMS (Cont.)