Aerco/protonode gateway, Gf-129, User manual – AERCO ProtoNode Gateway Rev 1 (with internal LEDs) User Manual
Page 42
![background image](/manuals/659313/42/background.png)
Page 42 of 64
USER MANUAL
AERCO/ProtoNode Gateway
OMM-0080_0D
AERCO International, Inc.
• 100 Oritani Dr. • Blauvelt, New York 10913 • Phone: 800-526-0288
VD2:011712
1
GF-129
Equipment
Point Name
Name
Read
Only
BACnet Type:ID
N2 Type
N2 ID
Lon SNVT NAME
Lon SNVT
Lon Direction
ModBus/Unit
Address
Blr Addr 7
01-Fire Rate Out
boilerstate_7
AV:100
data float
61
nvoBlrState7
inc count (9)
Output (non-polled)
30009/7
02-Active Setpoint
effectsetpt_7
AV:101
data float
62
nvoEffSetpt7
inc count (9)
Output (non-polled)
30017/7
03-Net Remote Setpt
setpt_7
AV:102
data float
63
nviSetpt7
inc count (9)
Input (non-polling)
40001/7
05-Fire Rate In
boilerload_7
AV:94
data float
65
nvoBlrLoad7
inc count (9)
Output (non-polled)
30018/7
06-Outlet Temp
localsuptemp_7
AV:95
data float
66
nvoLocSupTmp7
inc count (9)
Output (non-polled)
30003/7
07-Display Code
dispcode_7
AV:96
data float
67
nvoDispCode7
inc count (9)
Output (non-polled)
30001/7
08-Unit Status
unitstat_7
AV:97
data float
68
nvoUnitStat7
inc count (9)
Output (non-polled)
30002/7
09-Run Cycles
runcycles_7
AV:98
data float
69
nvoRunCycles7
51
Output (non-polled)
30012-30013/7
10-Run Hours
runhours_7
AV:99
data float
70
nvoRunHours7
51
Output (non-polled)
30014-30015/7
Blr Addr 8
01-Fire Rate Out
boilerstate_8
AV:110
data float
71
nvoBlrState8
inc count (9)
Output (non-polled)
30009/8
02-Active Setpoint
effectsetpt_8
AV:111
data float
72
nvoEffSetpt8
inc count (9)
Output (non-polled)
30017/8
03-Net Remote Setpt
setpt_8
AV:112
data float
73
nviSetpt8
inc count (9)
Input (non-polling)
40001/8
05-Fire Rate In
boilerload_8
AV:104
data float
75
nvoBlrLoad8
inc count (9)
Output (non-polled)
30018/8
06-Outlet Temp
localsuptemp_8
AV:105
data float
76
nvoLocSupTmp8
inc count (9)
Output (non-polled)
30003/8
07-Display Code
dispcode_8
AV:106
data float
77
nvoDispCode8
inc count (9)
Output (non-polled)
30001/8
08-Unit Status
unitstat_8
AV:107
data float
78
nvoUnitStat8
inc count (9)
Output (non-polled)
30002/8
09-Run Cycles
runcycles_8
AV:108
data float
79
nvoRunCycles8
51
Output (non-polled)
30012-30013/8
10-Run Hours
runhours_8
AV:109
data float
80
nvoRunHours8
51
Output (non-polled)
30014-30015/8
Blr Addr 9
01-Fire Rate Out
boilerstate_9
AV:120
data float
81
nvoBlrState9
inc count (9)
Output (non-polled)
30009/9
02-Active Setpoint
effectsetpt_9
AV:121
data float
82
nvoEffSetpt9
inc count (9)
Output (non-polled)
30017/9
03-Net Remote Setpt
setpt_9
AV:122
data float
83
nviSetpt9
inc count (9)
Input (non-polling)
40001/9
05-Fire Rate In
boilerload_9
AV:114
data float
85
nvoBlrLoad9
inc count (9)
Output (non-polled)
30018/9
06-Outlet Temp
localsuptemp_9
AV:115
data float
86
nvoLocSupTmp9
inc count (9)
Output (non-polled)
30003/9
07-Display Code
dispcode_9
AV:116
data float
87
nvoDispCode9
inc count (9)
Output (non-polled)
30001/9
08-Unit Status
unitstat_9
AV:117
data float
88
nvoUnitStat9
inc count (9)
Output (non-polled)
30002/9
09-Run Cycles
runcycles_9
AV:118
data float
89
nvoRunCycles9
51
Output (non-polled)
30012-30013/9
10-Run Hours
runhours_9
AV:119
data float
90
nvoRunHours9
51
Output (non-polled)
30014-30015/9
C.2.3 - Twelve C-Mores and One ACS/BMS II/BMS (Cont.)