Aerco/protonode gateway, Gf-129, User manual – AERCO ProtoNode Gateway Rev 1 (with internal LEDs) User Manual

Page 42

background image

Page 42 of 64

USER MANUAL

AERCO/ProtoNode Gateway

OMM-0080_0D

AERCO International, Inc.

• 100 Oritani Dr. • Blauvelt, New York 10913 • Phone: 800-526-0288

VD2:011712
1

GF-129

Equipment

Point Name

Name

Read
Only

BACnet Type:ID

N2 Type

N2 ID

Lon SNVT NAME

Lon SNVT

Lon Direction

ModBus/Unit
Address

Blr Addr 7

01-Fire Rate Out

boilerstate_7

AV:100

data float

61

nvoBlrState7

inc count (9)

Output (non-polled)

30009/7

02-Active Setpoint

effectsetpt_7

AV:101

data float

62

nvoEffSetpt7

inc count (9)

Output (non-polled)

30017/7

03-Net Remote Setpt

setpt_7

AV:102

data float

63

nviSetpt7

inc count (9)

Input (non-polling)

40001/7

05-Fire Rate In

boilerload_7

AV:94

data float

65

nvoBlrLoad7

inc count (9)

Output (non-polled)

30018/7

06-Outlet Temp

localsuptemp_7

AV:95

data float

66

nvoLocSupTmp7

inc count (9)

Output (non-polled)

30003/7

07-Display Code

dispcode_7

AV:96

data float

67

nvoDispCode7

inc count (9)

Output (non-polled)

30001/7

08-Unit Status

unitstat_7

AV:97

data float

68

nvoUnitStat7

inc count (9)

Output (non-polled)

30002/7

09-Run Cycles

runcycles_7

AV:98

data float

69

nvoRunCycles7

51

Output (non-polled)

30012-30013/7

10-Run Hours

runhours_7

AV:99

data float

70

nvoRunHours7

51

Output (non-polled)

30014-30015/7

Blr Addr 8

01-Fire Rate Out

boilerstate_8

AV:110

data float

71

nvoBlrState8

inc count (9)

Output (non-polled)

30009/8

02-Active Setpoint

effectsetpt_8

AV:111

data float

72

nvoEffSetpt8

inc count (9)

Output (non-polled)

30017/8

03-Net Remote Setpt

setpt_8

AV:112

data float

73

nviSetpt8

inc count (9)

Input (non-polling)

40001/8

05-Fire Rate In

boilerload_8

AV:104

data float

75

nvoBlrLoad8

inc count (9)

Output (non-polled)

30018/8

06-Outlet Temp

localsuptemp_8

AV:105

data float

76

nvoLocSupTmp8

inc count (9)

Output (non-polled)

30003/8

07-Display Code

dispcode_8

AV:106

data float

77

nvoDispCode8

inc count (9)

Output (non-polled)

30001/8

08-Unit Status

unitstat_8

AV:107

data float

78

nvoUnitStat8

inc count (9)

Output (non-polled)

30002/8

09-Run Cycles

runcycles_8

AV:108

data float

79

nvoRunCycles8

51

Output (non-polled)

30012-30013/8

10-Run Hours

runhours_8

AV:109

data float

80

nvoRunHours8

51

Output (non-polled)

30014-30015/8

Blr Addr 9

01-Fire Rate Out

boilerstate_9

AV:120

data float

81

nvoBlrState9

inc count (9)

Output (non-polled)

30009/9

02-Active Setpoint

effectsetpt_9

AV:121

data float

82

nvoEffSetpt9

inc count (9)

Output (non-polled)

30017/9

03-Net Remote Setpt

setpt_9

AV:122

data float

83

nviSetpt9

inc count (9)

Input (non-polling)

40001/9

05-Fire Rate In

boilerload_9

AV:114

data float

85

nvoBlrLoad9

inc count (9)

Output (non-polled)

30018/9

06-Outlet Temp

localsuptemp_9

AV:115

data float

86

nvoLocSupTmp9

inc count (9)

Output (non-polled)

30003/9

07-Display Code

dispcode_9

AV:116

data float

87

nvoDispCode9

inc count (9)

Output (non-polled)

30001/9

08-Unit Status

unitstat_9

AV:117

data float

88

nvoUnitStat9

inc count (9)

Output (non-polled)

30002/9

09-Run Cycles

runcycles_9

AV:118

data float

89

nvoRunCycles9

51

Output (non-polled)

30012-30013/9

10-Run Hours

runhours_9

AV:119

data float

90

nvoRunHours9

51

Output (non-polled)



30014-30015/9