C.2 BACnet/IP, BACnet MS/TP, Metasys N2, and LonWorks Points List

C.2.1 - Four C-Mores and One ACS/BMS II/BMS

Equipment

Point Name

Name

Read Only BACnet Type:ID N2 Type N2 ID Lon SNVT NAME Lon SNVT

Lon Direction

ModBus/Unit Addr.

Blr Addr 1

01-Fire Rate Out

boilerstate_1

AV:26

data float 1 nvoBlrState1

inc count (9) Output (non-polled)

30009/1

02-Active Setpoint

effectsetpt_1

AV:27

data float 2 nvoEffSetpt1

inc count (9) Output (non-polled)

30017/1

03-Net Remote Setpt setpt_1

AV:24

data float 3 nviSetpt1

inc count (9) Input (non-polling)

40001/1

05-Fire Rate In

boilerload_1

AV:28

data float 5 nvoBlrLoad1

inc count (9) Output (non-polled)

30018/1

06-Outlet Temp

localsuptemp_1

AV:29

data float 6 nvoLocSupTmp1 inc count (9) Output (non-polled)

30003/1

07-Display Code

dispcode_1

AV:22

data float 7 nvoDispCode1 inc count (9) Output (non-polled)

30001/1

08-Unit Status

unitstat_1

AV:23

data float 8 nvoUnitStat1

inc count (9) Output (non-polled)

30002/1

09-Run Cycles

runcycles_1

AV:42

data float 9 nvoRunCycles1 51

Output (non-polled)

30012-30013/1

10-Run Hours

runhours_1

AV:43

data float 10 nvoRunHours1 51

Output (non-polled)

30014-30015/1

Blr Addr 2

01-Fire Rate Out

boilerstate_2

AV:30

data float 11 nvoBlrState2

inc count (9) Output (non-polled)

30009/2

02-Active Setpoint

effectsetpt_2

AV:46

data float 12 nvoEffSetpt2

inc count (9) Output (non-polled)

30017/2

03-Net Remote Setpt setpt_2

AV:47

data float 13 nviSetpt2

inc count (9) Input (non-polling)

40001/2

05-Fire Rate In

boilerload_2

AV:50

data float 15 nvoBlrLoad2

inc count (9) Output (non-polled)

30018/2

06-Outlet Temp

localsuptemp_2

AV:51

data float 16 nvoLocSupTmp2 inc count (9) Output (non-polled)

30003/2

07-Display Code

dispcode_2

AV:52

data float 17 nvoDispCode2 inc count (9) Output (non-polled)

30001/2

08-Unit Status

unitstat_2

AV:53

data float 18 nvoUnitStat2

inc count (9) Output (non-polled)

30002/2

09-Run Cycles

runcycles_2

AV:44

data float 19 nvoRunCycles2 51

Output (non-polled)

30012-30013/2

10-Run Hours

runhours_2

AV:45

data float 20 nvoRunHours2 51

Output (non-polled)

30014-30015/2

Blr Addr 3

01-Fire Rate Out

boilerstate_3

AV:54

data float 21 nvoBlrState3

inc count (9) Output (non-polled)

30009/3

02-Active Setpoint

effectsetpt_3

AV:55

data float 22 nvoEffSetpt3

inc count (9) Output (non-polled)

30017/3

03-Net Remote Setpt setpt_3

AV:56

data float 23 nviSetpt3

inc count (9) Input (non-polling)

40001/3

05-Fire Rate In

boilerload_3

AV:60

data float 25 nvoBlrLoad3

inc count (9) Output (non-polled)

30018/3