4.2.4 Previous value comparison function [d]
Compares the average of the previously measured values with the current
measured value and displays only abrupt changes among slow changes.
When any hold function (peak hold, peak-to-peak hold or sample hold) is used, this
function is effective to ignore small differences caused by temperature fluctuation
or the unstable status during warm-up time.
Note: If the displayed value is out of the preset tolerance range, the input value is
not used in the comparison calculation of the next input.
Setting function "d"
1. Press the
key for at least 2 seconds.
The sensor enters the common function selection mode.
2. Press the
key to make function "d" flash.
3. Press the
or
key to select the previous value comparison function.
4. Press the
key to select the desired function number.
5. Press the
key.
The sensor saves the setting and returns to the measurement state.
Note: To reset the values used for the previous value comparison, short-circuit the
No. 11 reset terminal and GND terminal.
HIOUT
ON
OFF
Slow changes
Abrupt change
Hold value
(Time)
Enable the previous value
comparison function
Disable the previous value
comparison function