11 technical details, 1 technical details – Pilz PSENvip RL D P User Manual
Page 141

11.1
Technical details
11
Technical details
Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]
11-2
The standards valid on 2010-03 apply.
SI_Kennzahlen_PSENvip
Safety characteristic data
Si_Kennzahlen_Erläuterung_1
All the units used within a safety function must be considered when cal-
culating the safety characteristic data.
OSSD in accordance with EN 61496-1, type 4
Signal level at "0"
0 V DC (-3 V ... 2 V in accordance with EN 61496)
Signal level at "1"
UB - 1 VDC (11 V ... 30 V in accordance with EN 61496)
Residual current at "0" signal
Max. 1 mA (<2 mA in accordance with EN 61496)
Duration of on and off time during self test
40 µs
Max. cable resistance for detection of shorts between con-
tacts
16 Ohm
Max. capacitive load
20 nF for R
L
> 48 ohms with rated voltage
Max. inductive load
0.5 H
Overrun measurement
Signal level at "0"
0 VDC (-3 V ... 2 V)
Signal level at "1"
UB - 1 VDC (11 V ... 30 V)
Residual current at "0" signal
Max. 1 mA
Max. capacitive load
250 nF at 0 ... 500 mA
Transmitter synchronisation
Max. capacitive load
500 nF
Environmental data
Protection type (EN 60529)
IP54
Ambient temperature
0 °C… 50 °C
(EN 60068-2-14)
Storage temperature
-35 °C… 70 °C
(EN 60068-2-1, EN 60068-2-2)
Climatic suitability
93 % rel. h. at 40 °C
(EN 60068-2-78)
Condensation
Not permitted
Vibration
Frequency range: 10 Hz … 55 Hz
(EN 60068-2-6)
Amplitude: 0.35 mm
20 cycles per axis
Shock
(EN 60068-2-29)
10 g, 16 ms
EMC
EN 61000-6-4, EN 61496-1
Mechanical data
Dimensions (H x W x D)
Transmitter
115.5 mm x 112 mm x 168 mm
Receiver
115.5 mm x 112 mm x 228 mm
Weight
Transmitter
1700 g
Receiver
2900 g
Unit
Operating mode
EN ISO 13849-1
PL
EN 954-1
Category
EN IEC 62061
SIL CL
PFH [1/h]
t
M
[year]
PSENvip
---
PL e (Cat. 4)
Cat. 4
SIL CL 3
5.08E-9
(T = 40 °C)
20
Outputs on the receiver