3 fatal error, 9diagnostics and troubleshooting, 1 troubleshooting – Pilz PSENvip RL D P User Manual

Page 116

background image

Pilz GmbH & Co. KG, Felix-Wankel-Straße 2, 73760 Ostfildern, Germany
Telephone: +49 711 3409-0, Telefax: +49 711 3409-133, E-Mail: [email protected]

9-3

9.1

Troubleshooting

9

Diagnostics and Troubleshooting

Reaction of the PSENvip

The PSENvip switches to a STOP state.

Outputs OSSD1/OSSD2 on the receiver are switched off.

In this state, operation is no longer possible. However, diagnostics
are available.

Remedy

Note the error message (see section entitled "Error messages").

Rectify the error.

Restart the PSENvip: Switch supply voltage off and then on again.

9.1.3

Fatal Error

Fatal Error

9-

Diagnose_Fehlerbehandlung_fatale_Fehler

Possible causes

Major system defect

Error during self-test

Reaction of the PSENvip

The PSENvip switches to a FATAL state. It remains in a safe condi-
tion.

Outputs OSSD1/OSSD2 on the receiver are switched off.

The transmitter's light source goes out.

In this state, operation is no longer possible. The display is no longer
operable. Diagnostics are no longer available.

Remedy

It is not possible for the user to rectify the error.

Note the conditions under which the error occurred.

Restart the PSENvip: Switch supply voltage off and then on again.

The error message will not be displayed. However, it will be possible
to select the DIAGNOSTICS menu.

Note the error message (see section entitled "Error messages").

Contact Pilz.