SAE-1111/1112/1162 Carbon Monoxide (CO) Detectors
5
Installation Guide
When a value is changed, press the
save it to memory and advance to the next menu
item.
Press
CO Range = 0–300 ppm
Press the
able options. The CO sensing range and output
scale can be changed to 0 to 100 ppm, 0 to 150
ppm, 0 to 300 ppm, 0 to 400 ppm, or 0 to 500 ppm.
Press the
factory default CO Range is 0 to 300 ppm.
Press
Buzzer = Enable
Use the
buzzer alarm. When disabled, the buzzer will not
sound if the buzzer trip point is exceeded. The
buzzer will still beep on startup and will still beep
for a fault alarm (if enabled). Press
save the setting. The factory default is Enable.
Press
Buzzer Trip = 150
Use the
able options. The buzzer alarm trip point may be
set from 0 to 500 ppm in 10 ppm increments. Press
is 150 ppm. (This item will not be shown if the
buzzer is disabled.)
Press
Buzzer Del = 5Min
Use the
able options. The buzzer delay may be set from
0 to 10 minutes in 1 minute increments. Press
is 5 minutes. (This item will not be shown if the
buzzer is disabled.)
Press
Buzzer Test = OFF
Use the
during test mode or disable it (OFF). Press
Off. (This item will not be shown if the buzzer is
disabled.)
Press
Relay 1 TRIP = 50
Use the
able options. The Relay 1 alarm trip point may
be set from 20 to 500 ppm in 10 ppm increments.
Press
default is 50 ppm. (This item will not be shown if
Relay 1 is not installed.)
Press
Relay 1 Hyst = 10
Use the
able options. The Relay 1 hysteresis (deadband)
may be set from 10 to 100 ppm in 5 ppm incre-
ments. Press
factory default is 10 ppm. Note that the maximum
value may be limited by the trip-point value. (This
item will not be shown if Relay 1 is not installed.)
Press
Relay 1 DEL = 2MIN
Use the
able options. The Relay 1 delay may be set from
0 to 10 minutes in 1 minute increments. Press
2 minutes. (This item will not be shown if Relay 1
is not installed.)
Press
Relay 1 Test = OFF
Use the
ing test mode or disable it (OFF). Press
to save the setting. The factory default is Off. (This
item will not be shown if Relay 1 is not installed.)
Press
Relay 2 Trip = 150
Use the
able options. The Relay 2 alarm trip point may
be set from 20 to 500 ppm in 10 ppm increments.
Press
default is 150 ppm. (This item will not be shown if
Relay 2 is not installed.)