Wiring, Wiring 2, Caution – KMC Controls SAE-1162 User Manual
Page 2

SAE-1111/1112/1162 Carbon Monoxide (CO) Detectors
2
Installation Guide
Use 22 AWG shielded wiring for all connections. Do
not locate device wires in the same conduit with wir-
ing used to supply inductive loads.
1. Connect the positive DC voltage, or the hot
side of the AC voltage, to the terminal marked
POWER (but do not apply power until all wiring
is completed and Volt/mA position is selected).
2. Connect the power supply common to the
terminal marked COM. The device is reverse
voltage protected and will not operate if
connected backwards.
NOTE: The detectors have a half-wave power
supply with the common the same as the
output signal common. If several units are
connected to one power supply, output
signals share the same signal common.
However, KMC recommends using a
separate transformer for each device.
CAUTION
Use caution when grounding the secondary of an
AC transformer, or when wiring multiple devices,
to ensure that the circuit ground point is the same
on all devices and the controller. See Application
Note AN0604D “Tips for connecting 24-volt power”
available from the KMC Controls web site or in the
SP-022 Digital Designer Guide.
3. Select the desired analog signal output switch
position for either Current (4–20 mA) or Voltage
(a menu item in the on-screen configuration
selects 0–5 VDC or 0–10 VDC).
CAUTION
The 4-20 mA current output signal operates in the
active mode and does not require a loop power
supply. The signal current is generated by the SAE-
11xx detector and must not be connected to a
powered input or device damage will result.
4. Set the input jumpers/pull-up resistors on the
KMDigital or BACnet controller for the desired
active voltage or current according to the
controller’s instructions.
5. Connect the detector’s OUT terminal to the
controller’s input (referenced to the COM
terminal) according to the illustration.
NOTE: See also Application Note AN0504L
“Connecting inputs and outputs to KMC
controllers” available from the KMC
Controls web site or in the SP-022 Digital
Designer Guide.
Wiring
4–20 mA Wiring and
Switch Setting
0–5/0–10 VDC Wiring
and Switch Setting
(Space Sensor Boards Shown Above—Switch and Terminal
Positions in Duct Sensors Have Altered Locations)