beautypg.com

Rockwell Automation AADvance Controller Safety Manual User Manual

Page 87

background image


Document: 553630
ICSTT-RM446K-EN-P Issue: 10

_C

4-31

Careful consideration should be given to the affect on the process of

using the 'hold last state' setting. The PFD & PFH data has been calculated on
the basis that the shutdown state is configured to the OFF state. Therefore the

OFF state shall be used for SIL2 and SIL3
An installed module automatically transitions from the Shutdown mode to the
Ready or Recover modes and hence to the Run mode when the RESET button

on the processor is pressed and the application is running.
The following conditions will also cause a module to enter the Shutdown
mode from the Ready, Recover or Run modes:

Stopping the application for any reason

Invalid calibration - the module will not be able to transition out of the

Shutdown mode until the module has been re-calibrated (module

calibration interval recommendation is every 2 years)

Disable line test

The digital output module incorporates line test functionality that can report

and indicate 'no load' field faults. This functionality can be enabled or disabled.

The settings are:

Yes - disables reporting and indication of 'no load' field faults

No - 'No load' field faults are reported and indicated

Availability of output modules

Output modules support redundancy when configured in dual operation using

the appropriate termination assembly. One redundant module may be inserted

or removed at any time without any impact on the safety function of the
system.

DO Termination assembly

The DO termination assembly is safety critical, it comes in two sizes —

simplex or dual. It has fuses for field output power and 8 field termination
connections for the output signals.

Analogue Output Module Safety Features

Analogue Output Module Safety Applications

The Analogue Output Module can be used in the following safety related

applications:

The fail-safe state current of the analogue output module is less than 2mA.

For energize to action high demand applications you must use dual

analogue output modules.

When the module is unlocked, all of its output channels (including any

channels set to hold last state) always go to the de-energized state.