AADvance is designed to meet the following industrial safety system

requirements:

NFPA 85 Requirements

NFPA 85:2007 provides minimum requirements for the design, installation,

operation and maintenance of large commercial industrial boilers, heat

recovery, heat recovery steam generators and related combustion systems.
The AADvance system is certified for use with NFPA 85 compliant systems.
The systems should be integrated in accordance with NFPA 85. In particular

the following shall be applied:

The operator shall be provided with a dedicated manual switch that shall

independently and directly actuate the safety shutdown trip relay. At least

one identified manual switch shall be located remotely from the boiler

where it can be reached in case of emergency.

The burner management system shall be provided with independent logic,
independent input/output systems, and independent power supplies and

shall be a functionally and physically separate device from other logic

systems, such as the control system for the boiler or heat recovery steam

generator.

Logic sequences or devices intended to cause a safety shutdown, once

initiated, shall cause a burner or master fuel trip, as applicable, and shall

require operator action prior to resuming operation of the affected plant.
No logic sequence or device shall be permitted that allows momentary

closing and subsequent inadvertent reopening of the main or ignition fuel

valves.

Documentation shall be provided to the owner and operator, indicating

that all safety devices and logic meet the requirements of the application.

System response time shall be sufficiently short to prevent negative effects

on the application.

The NFPA 85 certification is only applicable where the system is applied in

accordance with this safety manual and NFPA 85 requirements.