Power Frequency Magnetic Field immunity voltage Dips, Short interruptions and

Voltage Variations Immunity

BS EN 61000-4-8:1994

+ A1:2001 +

BS EN 6100-4-11:2004

30A rms/m, 50Hz and 60Hz Not Applicable

Immunity to Conducted Common Mode

Disturbance, 0 to 150
kHz

BS EN 61000-4-16:1998

+ A1:2004

DC & I/O Ports:

1 to 10V rms increasing at

20dB/decade from 1,5KHz to
15k Hz:

10V rms from 15k Hz to

150k Hz

100V rms for 1s at 16.6Hz,
50Hz and 60Hz 10V rms

continuous at 150Hz and
180Hz

None

Voltage Dips, Short Interruptions and Voltage Variations for DC Input Power

Ports

BS EN 61000-4-29:2001

40% for 10ms

0% for 20ms

The performance criteria for these
tests is fail-safe

Immunity to Electrostatic Discharge

Standards

Conditions

Notes

Tested to IEC 61000-
4-2

Air discharge ± 8 kV

Contact discharge ± 6 kV

None

If the anticipated EMI exceeds these levels, additional protection measures