Document: 553630

ICSTT-RM446K-EN-P Issue: 10

_C

Safety Manual (AADvance Controller)


Marine Certification

AADvance has been tested and found to comply with the EMC requirements
of BS EN 60945:2002. EMC compliance within a marine environment is

dependant on and can only be assured by the use of:

shielded Ethernet cables

adequate bonding of the system chassis to a suitable ground reference

Fit EMC Static Protection Covers

For EMC static protection you should fit the black plastic protection covers
(supplied with the base units) over any exposed 48 pin DIN connectors on the

T9300 I/O Base unit.

Using Shielded Cabling for Ethernet and Serial Ports

When using cable lengths that exceed 3m for Ethernet and Serial

communication you must use shielded cable to remain within the emission and
immunity standards. Also ensure that the shields are grounded to the

controller chassis.

Important: The system is resistant to radio interference due to its bus
structure. However, sensible use of site radios is advised; do not use

radios inside or near an open panel.

AADvance System Power Requirements

The AADvance controller is designed to operate from two independent 24V

dc power supplies with a common return path, that is, the 24V return shall be
common between the power feeds.