beautypg.com

Rockwell Automation AADvance Controller Safety Manual User Manual

Page 78

background image

4-22

Document: 553630

ICSTT-RM446K-EN-P Issue: 10

_C

Safety Manual (AADvance Controller)


AADvance also supports the ability to pass HART data between an external
Asset Management System (AMS) and Field Devices. This is strictly a passthru

mechanism using a dedicated AADvance HART DTM. This passthru capability

can however be enabled or disabled under application control.

HART data shall not be used as the primary process value for Safety

Functions as the HART protocol does not meet the required integrity levels

for Safety Instrumented Functions.

HART Passthru should be disabled if the field devices do not have

locked configuration, or if the device status is not monitored and alarmed to
prevent accidental or unauthorized changes to field device configuration.

HART devices have custom data which is provided in response to

HART command #03, the specific data for each device type must be used in

accordance with the device manufacturers published recommendations.