Processor functional safety configuration -24 – Rockwell Automation AADvance Controller Safety Manual User Manual
Page 80
![background image](/manuals/581708/80/background.png)
4-24
Document: 553630
ICSTT-RM446K-EN-P Issue: 10
_C
Safety Manual (AADvance Controller)
Processor Functional Safety Configuration
The T9110 Processor Module supports a limited set of configuration options;
the system will verify the hardware configuration, such as the module locations
against actual module types.
The processor module process safety time can be specified through the
AADvance Workbench and details are given in theAADvance Configuration
Guide , Rockwell Automation reference 553633
Processor Safety Functions
The processor module is classified as safety critical and is responsible for the
following safety functions:
solving application logic
external communication (Ethernet and serial)
communication with I/O modules such as receiving input values, sending
output values, coordinating diagnostics
enforcement of system PST
diagnostics, fault indications and degradation of the processor module
enforcement of input PST
diagnostics, fault indications and degradation of input modules
initiating diagnostics, fault declaration and for some fault conditions the
degradation of output modules
recovery mode operation
Reaction to faults in the processor module
The processor module reports faults by front panel indicators and fault codes
stored in the System Event log. SYSTEM HEALTHY and HEALTHY
LEDs go RED when a fault is detected in the processor module. Fault
indications are also sent to the user application by variables that you can set up
during the system configuration process. These variables provide the following
information:
module presence
module health and status
channel health and status
an echo of the front panel indications