beautypg.com

Processor functional safety configuration -24 – Rockwell Automation AADvance Controller Safety Manual User Manual

Page 80

background image

4-24

Document: 553630

ICSTT-RM446K-EN-P Issue: 10

_C

Safety Manual (AADvance Controller)


Processor Functional Safety Configuration

The T9110 Processor Module supports a limited set of configuration options;
the system will verify the hardware configuration, such as the module locations

against actual module types.
The processor module process safety time can be specified through the
AADvance Workbench and details are given in theAADvance Configuration

Guide , Rockwell Automation reference 553633

Processor Safety Functions

The processor module is classified as safety critical and is responsible for the
following safety functions:

solving application logic

external communication (Ethernet and serial)

communication with I/O modules such as receiving input values, sending

output values, coordinating diagnostics

enforcement of system PST

diagnostics, fault indications and degradation of the processor module

enforcement of input PST

diagnostics, fault indications and degradation of input modules

initiating diagnostics, fault declaration and for some fault conditions the

degradation of output modules

recovery mode operation

Reaction to faults in the processor module

The processor module reports faults by front panel indicators and fault codes
stored in the System Event log. SYSTEM HEALTHY and HEALTHY

LEDs go RED when a fault is detected in the processor module. Fault

indications are also sent to the user application by variables that you can set up

during the system configuration process. These variables provide the following
information:

module presence

module health and status

channel health and status

an echo of the front panel indications